Step 6 - Oil Burner; Step 7 - Oil Connections; Step 8 - Barometric Draft Control; Step 9 - Blocked Vent Shut- -Off (Bvso) For Chimney Venting - Bryant 374RAN Installation Instructions Manual

Multipoise oil furnace
Hide thumbs Also See for 374RAN:
Table of Contents

Advertisement

Step 6 — Oil Burner
This furnace is supplied with a high- -pressure atomizing retention
head- -type burner (for use with grade 1 or 2 Fuel Oil). The
mounting flange is fixed to burner air tube and no adjustment is
required for insertion length. The oil pump is set to operate on a
single line system. To operate on a two- -line system the by- -pass
plug must be installed.
Step 7 — Oil Connections
Complete instructions for installing fuel oil piping can be found in
oil burner Installation Instructions included with furnace.
Oil line entry holes are provided in side panels. Two holes are
provided in each location so that a 2- -pipe system may be used if
desired.
An oil filter should be installed as close to burner as possible with
ALL oil burners and is essential on lower firing rate burners. We
recommend the use of a low- -pressure- -drop oil filter such as the
General Filter, Inc. model #1A- -25A or equivalent.
Step 8 — Barometric Draft Control
The barometric draft control shipped with furnace MUST be used
with furnace to ensure proper operation. Instructions for installing
control are packed with control.
Step 9 — Blocked Vent Shut- - Off (BVSO) For Chimney
Venting
All oil furnaces installed in Canada must have a Blocked Vent
Shut- -Off.
Refer to Fig. 8- -13 and the installation instructions supplied with
the Blocked Vent Shut- -Off for installation and wiring procedures.
The Blocked Vent Shut- -Off must be installed in the flue between 2
in and 12 in from the furnace outlet and between the furnace outlet
and draft regulator. (See Fig. 9.)
Diagram B
Riello
Fig. 8 - - Wiring Diagram for Riello Burner
!
FIRE, CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury
or death.
Do not dent or scratch the surface of the thermal switch. The
thermal switch MUST be replaced if it is damaged.
!
FIRE, CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
DO NOT reset the device or restart the furnace unless the
cause of the interruption has been identified and corrected by
a qualified agency. Ensure that the Blocked Vent Shut- -Off
has been cleaned by a qualified agency before placing into
service. Annual inspection and cleaning of the Blocked Vent
Shut- -Off by a qualified agency is required.
!
FIRE, CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury,
death, and/or property damage.
The Blocked Vent Shut- -Off MUST be inspected and
maintained annually by a qualified agency.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Disconnect electrical power supply to the furnace before
wiring the Blocked Vent Shut- -Off.
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing, safety glasses, and
gloves when handling parts and servicing furnaces.
A06403
9
WARNING
WARNING
WARNING
WARNING
CAUTION

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents