11 DETERMININg ThE FLUE LENgTh AND FLUE pACKs REqUIRED CONT'D
Notes.
1. It is recommended that a support bracket is
fitted for every 1 metre of extension pipe used
and a bracket should be used at every joint, to
ensure pipes are held at the correct angle.
If a slip joint coupling is to be used then a
bracket should be used to secure the collar.
2. When extension 'D' packs are used the flue
duct MUST be inclined at 1.5 degrees to the
horizontal to allow condensate to drain back
into the boiler and out through the condensate
drain.
3. If the B pack, or telescopic B pack only are
used, they may be mounted horizontally. The
1.5 degrees is taken care of by the inclination of
the flue within the air pipe.
4. Only use water as a lubricant during assembly.
12 FLUE AssEMBLy - Exploded View
An optional flue duct extension kit is
required for wall thicknesses greater than
:
side
378mm
Rear
420mm
LEgEND
1. Duct assembly.
2. Flue turret.
3. Turret clamp.
telescopic b Pack shown
+
Ideal Logic
Combi -
INsTALLATION
3
Installation and Servicing
TELEsCOpIC FLUE
Total Flue length dimension
(measuring from CL of turret to outside wall)
Rear flue
Side flue
dim. x+155
dim. L+197
Up to 575 mm
Up to 575 mm
Up to 1525 mm
Up to 1525 mm
Up to 2475 mm
Up to 2475 mm
Up to 3425 mm
Up to 3425 mm
Up to 4375 mm
Up to 4375 mm
Up to 5325 mm
Up to 5325 mm
Up to 6275 mm
Up to 6275 mm
Up to 7225 mm
Up to 7225 mm
Up to 8175 mm
Up to 8175 mm
Up to 9000 mm
Up to 9000 mm
NON - TELEsCOpIC FLUE
Total Flue length dimension
(measuring from CL of turret to outside wall)
Rear flue
Side flue
dim. x+155
dim. L+197
Up to 640 mm
Up to 640 mm
Up to 1590 mm
Up to 1590 mm
Up to 2540 mm
Up to 2540 mm
Up to 3490 mm
Up to 3490 mm
Up to 4440 mm
Up to 4440 mm
Up to 5390 mm
Up to 5390 mm
Up to 6340 mm
Up to 6340 mm
Up to 7290 mm
Up to 7290 mm
Up to 8240 mm
Up to 8240 mm
Up to 9000 mm
Up to 9000 mm
2
Flue
Extra packs
Boiler
required
none
24,30 & 35
Pack D - 1 off
24,30 & 35
Pack D - 2 off
24,30 & 35
Pack D - 3 off
24, 30 & 35
Pack D - 4 off
24, 30 & 35
Pack D - 5 off
24, 30 & 35
Pack D - 6 off
24, 30 & 35*
Pack D - 7off
24 & 30
Pack D - 8 off
24 & 30**
Pack D - 9 off
*Logic Combi 35 is capable of 6m flue only
** Logic Combi 30 is capable of 8m flue only
Flue
Extra packs
Boiler
required
none
24,30 & 35
Pack D - 1 off
24,30 & 35
Pack D - 2 off
24,30 & 35
Pack D - 3 off
24, 30 & 35
Pack D - 4 off
24, 30 & 35
Pack D - 5 off
24, 30 & 35
Pack D - 6 off
24, 30 & 35*
Pack D - 7off
24 & 30
Pack D - 8 off
24 & 30**
Pack D - 9 off
*Logic Combi 35 is capable of 6m flue only
** Logic Combi 30 is capable of 8m flue only
TOP
1
The flue terminal MUST
be fitted with the 'TOP'
uppermost to allow the
correct fit and use of
the plume management
3G9499a
system.
size
24
size
24