Baxi Barcelona Installation And Servicing Instructions page 15

Wall mounted powered flue condensing boiler gas fired central heating unit
Hide thumbs Also See for Barcelona:
Table of Contents

Advertisement

7.0
Site Requirements – page 15
Fig. 18
Fig 18a
Pictorial examples of flue runs where EQUIVALENT flue
length equals 4m
Fig. 19
7.10
Flue Dimensions
See Section 1.2. The standard horizontal flue kit allows for
flue lengths between 270mm (10 5/8") and 800mm (32")
from elbow to terminal
(Fig. 18).
The maximum permissible equivalent flue length is:
4 metres (Fig. 18a).
NOTE: Each additional 45º of flue bend will account for an
equivalent flue length of 0.5m
eg. 45º = m,
90º = 2 x 45º = 1m etc.
7.11
Terminal Guard (Fig. 19)
1.
When codes of practice dictate the use of terminal
guards, they can be obtained from most Plumbers' and
Builders' Merchants.
2.
When ordering a terminal guard, quote the appliance
model number.
3.
The guard manufacturers listed below can be contacted
for terminal sizes and guard model numbers.
Tower Flue Components Ltd.,
Tower House,
Vale Rise,
Tonbridge,
Kent.
Tel: 01732 351555.
Quinnell, Barrett & Quinnell,
884 Old Kent Road,
London,
SE15 1NL.
Tel: 0171 639 1357.
4.
The flue terminal guard should be positioned centrally
over the terminal and fixed as illustrated
7.12
Vertical Flue
1.
Only a flue approved with the Baxi Barcelona can be
used.
2.
For information on vertical flues consult the Baxi
Barcelona Installer Guide or Notes for Guidance
supplied with the vertical flue pack.