Bryant 350AAV Installation, Start-Up, And Operating Instructions Manual page 34

Series a deluxe 4-way mulitpoise fixed-capacity condensing gas furnace
Hide thumbs Also See for 350AAV:
Table of Contents

Advertisement

NOTE:
Select 1 vent pipe connection and
1 combustion-air pipe connection.
AIR
FLOW
COMBUSTION-
COMBUSTION-
AIR
AIR
VENT
*
UPFLOW
COMBUSTION-
AIR
VENT
**
AIR
FLOW
HORIZONTAL-LEFT DISCHARGE
* For Non-Direct Vent (1-Pipe) system, orient elbow so that its
opening faces down.
** For Non-Direct Vent (1-Pipe) system, orient elbow so that its
opening faces sideways.
† An external trap kit (see furnace product data sheet) must be used.
Fig. 37—Combustion-Air and Vent Pipe
Connections
FIELD-SUPPLIED
2-IN. DIAMETER
PVC 90° ELBOW
COMBUSTION-AIR DISC
(FACTORY-SUPPLIED IN
LOOSE PARTS BAG)
LENGTH OF STRAIGHT PIPE PORTION OF
COMBUSTION-AIR INLET PIPE ASSEMBLY (IN.)
CASING WIDTH
17-1/2
21
24-1/2
Fig. 38—Combustion-Air Inlet Pipe Assembly
4. Insert assembled combustion air inlet pipe into intake
housing as shown in Fig. 37.
5. Drill a 1/8-in. hole in 2-in, combustion air pipe using the
hole in intake housing as a guide.
NOTE:
Select 1 vent pipe connection and
1 combustion-air pipe connection.
VENT
VENT
VENT
COMBUSTION-
COMBUSTION-
AIR
AIR
AIR
FLOW
DOWNFLOW
COMBUSTION-
AIR
VENT
**
HORIZONTAL-RIGHT DISCHARGE
FIELD-SUPPLIED
2-IN. DIAMETER
PVC PIPE
A
A
8-1/2 ± 1/2
10-1/2 ± 1/2
12 ± 1/2
6. Install a field-supplied No. 6 or No. 8 sheet metal screw into
combustion air pipe.
7. Install casing hole filler cap (factory-supplied in loose parts
bag) in unused combustion air pipe casing hole.
NOTE: Do not attach combustion air intake pipe permanently to
combustion air intake housing since it may be necessary to remove
pipe for service of igniter or flame sensor.
ATTACHMENT OF COMBUSTION AIR INTAKE HOUSING
*
PLUG FITTING
The combustion-air intake plug fitting must be installed in unused
combustion air intake housing. This fitting must be attached by
using RTV sealant, or by drilling a 1/8-in. hole in fitting, using
hole in intake housing as a guide. Install a field-supplied No. 6 or
No. 8 sheet metal screw.
AIR
FLOW
NOT IN
HORIZONTAL
SECTION
Fig. 39—Combustion-Air and Vent Pipe Diameter
Transition Location and Elbow Configuration
NOTE: DO NOT OVERTIGHTEN SCREW. Breakage of intake
A05092
housing or fitting may cause air leakage to occur.
A plugged drain connection has been provided on this fitting for
use when moisture is found in combustion air intake pipe and
combustion box. If use of this drain connection is desired, drill out
fitting's tap plug with 3/16-in. drill and connect a field-supplied
3/8-in. tube. This tube should be routed to open condensate drain
for furnace and A/C (if used), and should be trapped, as shown in
Fig. 40.
NOTE: (Direct Vent/2-Pipe System ONLY) Moisture in combus-
tion air intake may be a result of improper termination. Ensure
combustion air pipe termination is similar to those as shown in Fig.
40 so that it will not be susceptible to area where light snow or
others sources of moisture could be pulled in.
F. Vent Pipe
GENERAL
Furnace vent connection must be attached as shown in Fig. 37.
WARNING: CARBON MONOXIDE POISONING
AND PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in property
A96211
damage, personal injury, or death.
Vent pipes must be airtight.
NOTE: A 2-in. diameter pipe must be used within the furnace
casing. Make all pipe diameter transitions outside furnace casing
per Fig. 39.
The minimum vent pipe length for these furnaces is 5 ft. Short pipe
lengths (5-8 ft) may discharge condensate droplets. These conden-
sate droplets may be undesirable. A 12-in. minimum offset pipe
section is recommended to reduce excessive condensate droplets
from exiting vent pipe outlet. (See Fig. 41)
—34—
FURNACE
PIPE DIAMETER
TRANSITION IN
VERTICAL SECTION
A93034