Chapter 4 - Specifications; General Specifications; Electrical Specifications - Emerson 110V User Manual

Network power switch single pole 110v
Table of Contents

Advertisement

User Manual

4 Chapter 4 - Specifications

4.1 General Specifications

Manual and Automatic Transfers
Sense and transfer time – less than 6 milliseconds
Break-Before make switching
Selectable preferred source
Selectable auto/manual retransfer
In-phase transfer window – adjustable from 5 ± 1°
Convection cooling
Hot swappable electronic static switching module
Live mimic on Hot swappable unit for indicating load supply status & alarms
Make before break manual bypass switch to transfer load from static switch to direct source 1 or source 2

4.2 Electrical Specifications

ELECTRICAL
CHARACTERISTICS
Nominal Input Voltage
Nominal Output current
Frequency
Source unhealthy status
Load Power factor range
Load Crest factor
In-Phase transfer window
Source voltage distortion
Overload capability
Over current Protection
Short circuit withstand
capability
Redundant Control Power
supplies
Integral Maintenance Bypass
Alarm contacts
Unsynchronised transfer
N
e
t
w
o
r
k
P
o
w
e
r
S
w
N
e
t
w
o
r
k
P
o
w
e
r
S
w
UNITS
110, 115 or 120 volts singe phase, 3W+G, 50 Hz. Solidly grounded
Volts
Amps
Hz
Guaranteed Transfer to alternate source within –15 % of Vnominal
-
-
-
-
%
%
125% of continuous current for 2 hrs, 1000% for two cycles minimum.
-
Amps
upto 20,000 symmetrical amps, protected by internal fusing.
-
taken from available source 1 and source 2
-
-
Eight Isolated Normally Open alarm & static switch Status contacts.
6 milllisec for synchronized transfer and 16 millisec for unsynchronized
Chapter 3 – Installation Procedure
i
t
c
h
i
t
c
h
DESCRIPTION
power sources
25
50 / 60
0.5 to unity leading or lagging
upto 3.5
Adjustable from 5 ± 1º
up to 10% THD
By semi conductor fuse
Make before break operation
transfer.
Page 4-1