INTRODUCTION

The Liebert UPStation S™ Uninterruptible power supply
(UPS) system protects valuable equipment, data, and
processes from utility power disturbances.
performance, on-line, microprocessor-controlled design
ensures clean, regulated, sinewave power to loads
regardless of utility power fluctuations. An internal battery
provides power to loads during utility power outages.
This highly intelligent UPS alerts you to unusual
circumstances, or configure the UPS to serve as a source
of information and a power control base for specific
applications.
Programmable
interfaces, and several network control features (remote
status/control, Power Management, event logging, and
others) provide maximum application flexibility.

Features

Input power factor correction (PFC) makes optimal
use of utility power.
Input current total harmonic distortion (THD) of less
than 5% minimizes noise on the branch circuit and
reduces neutral currents.
Power Output Distribution (unit) facilitates UPS repair
or battery replacement without disrupting power to the
load on 3.5 - 6 kVA units
Temperature-compensated
longer battery life.
Programmable voltage and frequency.
Tower configuration with small footprint.
Two-phase pulse width modulated (PWM) inverter
with isolated neutral.
UL 1778 and CSA 22.2 listed for user safety.

Standard System Components

Integral Battery
LCD Display for comprehensive user indications and
controls
Audible Alarm
Remote Emergency Power Off (REPO) capability
Auto-Restart capability
Automatic Bypass

Optional System Components

Communication Interfaces: SiteNet 1 Shutdown Kits,
SiteNet 2 Power Surveillance, and SiteNet SNMP
External battery cabinets
Power Management for individual load control.
The high-
parameters,
computer
battery
recharge
for

UNLOADING THE UPS

Refer to the figures below:
1.
Remove shipping bands (A) and edge protectors (B).
2.
Remove polybag and box.
3.
Remove bracket mounting bolts (C) from pallet.
4.
Knock out shims (D) with hammer and screwdriver.
5.
Thread leveling feet (E) flush with unit bottom.
6.
Remove front pallet hex bolts (F). Remove the front
skid (G).
7.
Slowly tilt the unit forward and roll it off the pallet.
CAUTION: The units are heavy. Use at least two
people for this step.
Unbolt shipping brackets (H) from unit.
Verify model number and check for damage. Make sure
UPS Input, Output, and Battery circuit breakers are Open
(OFF).
Figure #2
6
Inspect unit.
FIGURE #1
Side View with
Mounting Bracket
Detail