8-18 kVA UPS Connections
The 8-18 kVA Liebert UPStation S™ allows the customer
to connect a three-phase input if desired. The only benefit
to connecting a third phase is to balance a three-phase
feed transformer.
The 8-18 kVA Liebert UPStation S™ has two basic
connections; UPS Input and UPS Output. Below is an
1. Input and Output Power wiring must be run in separate conduit.
2. Control and Power wiring must be run in separate conduit.
3. Wire and breaker sizing must be in accordance with NEC and
local electrical codes.
4. RMBP units are designed to be mounted on the wall. Insure that
wall can support weight prior to installation.
5. The UPStation S must have an internal bypass for system to
operate according to specifications.
illustration of how the system will look electrically once the
installation is complete.
Connections between the maintenance bypass and the
UPS must be run in separate conduit.
clearance requirements for service on the UPS, it is
recommended that flexible conduit be used.
UPStation S™
21
Due to the