Wiring Preparation

WARNING: Please read this section thoroughly
before attempting to install wiring to this unit.
Be sure that the unit is not connected to any AC
utility power source before installing any wiring
to this unit. This UPS should be installed by a
qualified / certified electrician.
Removing the Cover Plates
On the back of the
UPS, cover plates
are over the input
and output
terminals, as
shown on right.
Remove these
using a Phillips
screwdriver. Keep
screws and plates
to one side.
Configuring the Bypass Voltage (TB2)
The UPS voltage is factory set to 208V. Should
the user have a utility supply of 240V, the
bypass voltage jumper will have to be changed
to ensure correct output voltage.
Cable Installation

Power Cable Installation

Refer to the charts below when selecting cables:
Max Input
Current
Input
Protection
Max Output
Current
Input / Output
Terminal
Details
90°C rated copper wire is recommended
Notes:
If the start-up is on bypass the UPS has a 3-
cycle inrush current that is 6 times the rated
output current. This must be taken into account
when selecting the overload protection device at
the AC input supply distribution point. To avoid
random tripping on start up, it is recommended
that the AC input supply be protected with a
circuit breaker capable of withstanding this initial
inrush.
This UPS is fitted with EMI suppression filters.
Earth leakage current is less than 40mA.
Transient and steady state earth leakage
currents
equipment. This should be taken into account
when
devices, as the earth leakage currents of both
the UPS and load will be carried.
Input and output cables must be run in separate
conduits.
A branch rated overcurrent protection device
(circuit breaker or fused disconnect switch) must
be installed for the AC output.
14
Power Cable and Protection Ratings
120V
208V
79 A
100 A
67A /
77 A
phase
2 AWG max (35 mm²)
6 AWG min (16 mm²)
Torque Rating: 22-26 in/lb
may
occur
when
selecting
ground
current
240V
69 A
90 A
67 A
(2.5-3 nm)
starting
the
detection