Installation Process; Outside Units Information - LG Multi V ARWN Series Installation Manual

Hide thumbs Also See for Multi V ARWN Series:
Table of Contents

Advertisement

4

INSTALLATION PROCESS

Indicate clearly who will be responsible for switch setting.
Determination of division work
Make connection clearly between outside, indoor,
Preparation of contract drawings
remote controller and option.
Take account of gradient
Sleeve and insert work
of drain piping
Check model name to
Installation of indoor unit
make sure the fitting
is made correctly
Special attention to dryness,
Refrigerant piping work
cleanness and tightness
Drain pipe work
Adjust to downward gradient
Make sure airflow is sufficient
Duct work
Make sure no gaps are left where
Heat insulation work
the insulating materials are joined
Electrical work
Multiple core cable must not be used.
(connection circuits and drive circuits)
(suitable cable should be selected)
In the final check for 24hours at 3.8 MPa(38.7 kgf/cm
Airtight test
must be no drop in pressure.
The vacuum pump used must have a capacity of reaching at least
Vacuum drying
5 torr, more than 1 hour
Recharge correctly as calculated in this manual. and record the
Additional charge of refrigerant
amount of added refrigerant
Make sure there are no gaps left between the facing materials
Fit facing panels
used on the ceiling
Refer to automatic addressing flowchart
Automatic addressing of indoor unit
Preheat the crank case with the electrical heater for more than 6 hours.
Run each indoor unit in turn to make sure the pipe work
Test run adjustment
has been fitted correctly
Explain the use of the system as clearly as possible to your customer and
Transfer to customer with explanation
make sure all relevant documentation is in order
!
CAUTION
• The above list indicates the order in which the individual work
operations are normally carried out but this order may be varied
where local conditions warrants such change.
• The thickness of the piping should comply with the relevant
local and national regulations for the designed pressure 3.8MPa.
• Since R410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state.(If the refrigerant
is charged in its gaseous state, its composition changes and the
system will not work properly.)

OUTSIDE UNITS INFORMATION

CAUTION
!
• Ratio of the running Indoor Units to the Outside: Within 10 ~ 100%
• A combination operation over 100% cause to reduce each indoor unit capacity.
Combination Ratio(50~200%)
Outside Unit Number
Single outside unit s
Double outside unit s
More than Triple outside unit s
Notes: * We can guarantee the operation only within 130% Combina-
tion. If you want to connect more than 130% combination,
please contact us and discuss the requirement like below.
• If the operation of indoor unit is more than 130%, low airflow
operation is recommended in all the indoor units.
• If the operation of indoor unit is more than 130%, additional re-
frigerant is needed according to the Aheadquarter guidance.
• Over 130%, capacity is same as capacity of 130%, Same re-
mark is valid for power input.
Outside unit foundation work
The foundation must be level even
Installation of outside unit
Avoid short circuits and ensure
sufficient space is allowed for service
2
) there
Connection Ratio
200%
160%
130%
Power Supply : 3Φ, 380-415V, 50Hz
Model Name : ARWN***LAS4
Unit
System Capacity (HP)
8
Combination Unit
ARWN080LAS4
Model
Independent Unit
ARWN080LAS4
Refrigerant Precharged Amount
kg
5.5
Maximum Connectable Number of Indoor Units
13
kg
127 x 1
Net Weight
lbs
280 x 1
mm
755 × 997 × 500
Dimensions(WxHxD)
inch
(29-23/32 x 39-1/4 x 19-11/16) x 1 (29-23/32 x 39-1/4 x 19-11/16) x 1 (29-23/32 x 39-1/4 x 19-11/16) x 1
Liquid
mm(inch)
9.52(3/8)
Refrigerant
Connecting Pipes
Gas
mm(inch)
22.2(7/8)
Inlet
mm
PT 40
Water Connect-
Outlet
mm
PT 40
ing Pipes
Drain Outlet
mm
20
Cooling
10°C ~ 45°C(50°F ~ 113°F)
Temp. range of
Circulation water
Heating
-5°C ~ 45°C(23°F ~ 113°F)
Unit
System Capacity (HP)
Combination Unit
ARWN140LAS4
Model
Independent Unit
ARWN140LAS4
Refrigerant Precharged Amount
kg
Maximum Connectable Number of Indoor Units
kg
127 x 1
Net Weight
lbs
280 x 1
mm
755 × 997 × 500
Dimensions(WxHxD)
inch
(29-23/32 x 39-1/4 x 19-11/16) x 1 (29-23/32 x 39-1/4 x 19-11/16) x 1
Liquid
mm(inch)
12.7(1/2)
Refrigerant
Connecting Pipes
Gas
mm(inch)
25.4(1)
Inlet
mm
Water Connect-
Outlet
mm
ing Pipes
Drain Outlet
mm
Cooling
10°C ~ 45°C(50°F ~ 113°F)
Temp. range of
Circulation water
Heating
-5°C ~ 45°C(23°F ~ 113°F)
Unit
System Capacity (HP)
Combination Unit
ARWN180LAS4
Model
Independent Unit
ARWN180LAS4
Refrigerant Precharged Amount
kg
Maximum Connectable Number of Indoor Units
kg
140 x 1
Net Weight
lbs
309 x 1
mm
755 × 997 × 500
Dimensions(WxHxD)
inch
(29-23/32 x 39-1/4 x 19-11/16) x 1 (29-23/32 x 39-1/4 x 19-11/16) x 1
Liquid
mm(inch)
12.7(1/2)
Refrigerant
Connecting Pipes
Gas
mm(inch)
28.58(1-1/8)
Inlet
mm
Water Connect-
Outlet
mm
ing Pipes
Drain Outlet
mm
Cooling
10°C ~ 45°C(50°F ~ 113°F)
Temp. range of
Circulation water
Heating
-5°C ~ 45°C(23°F ~ 113°F)
Unit
System Capacity (HP)
22
Combination Unit
ARWN220LAS4
Model
ARWN120LAS4
Independent Unit
ARWN100LAS4
Refrigerant Precharged Amount
kg
3.5 + 3.4
35
Maximum Connectable Number of Indoor Units
127 x 2
kg
Net Weight
280 x 2
lbs
(755 × 997 × 500) x 2
mm
Dimensions(WxHxD)
(29-23/32 x 39-1/4 x 19-11/16) x 2 (29-23/32 x 39-1/4 x 19-11/16) x 2 (29-23/32 x 39-1/4 x 19-11/16) x 2
inch
19.05(3/4)
Liquid
mm(inch)
Refrigerant
Connecting Pipes
34.9(1-3/8)
Gas
mm(inch)
PT 40 + PT 40
Inlet
mm
Water Connect-
PT 40 + PT 40
Outlet
mm
ing Pipes
20
Drain Outlet
mm
10°C ~ 45°C(50°F ~ 113°F) 10°C ~ 45°C(50°F ~ 113°F) 10°C ~ 45°C(50°F ~ 113°F)
Cooling
Temp. range of
Circulation water
-5°C ~ 45°C(23°F ~ 113°F) -5°C ~ 45°C(23°F ~ 113°F) -5°C ~ 45°C(23°F ~ 113°F)
Heating
1 Unit
10
12
ARWN100LAS4
ARWN120LAS4
ARWN100LAS4
ARWN120LAS4
3.4
3.5
16
20
127 x 1
127 x 1
280 x 1
280 x 1
755 × 997 × 500
755 × 997 × 500
9.52(3/8)
12.7(1/2)
22.2(7/8)
25.4(1)
PT 40
PT 40
PT 40
PT 40
20
20
10°C ~ 45°C(50°F ~ 113°F)
10°C ~ 45°C(50°F ~ 113°F)
-5°C ~ 45°C(23°F ~ 113°F)
-5°C ~ 45°C(23°F ~ 113°F)
1 Unit
14
16
ARWN160LAS4
ARWN160LAS4
5.8
3
23
26
140 x 1
309 x 1
755 × 997 × 500
12.7(1/2)
28.58(1-1/8)
PT 40
PT 40
PT 40
PT 40
20
20
10°C ~ 45°C(50°F ~ 113°F)
-5°C ~ 45°C(23°F ~ 113°F)
1 Unit
18
20
ARWN200LAS4
ARWN200LAS4
3
3
29
32
140 x 1
309 x 1
755 × 997 × 500
12.7(1/2)
28.58(1-1/8)
PT 40
PT 40
PT 40
PT 40
20
20
10°C ~ 45°C(50°F ~ 113°F)
-5°C ~ 45°C(23°F ~ 113°F)
2 Unit
24
26
ARWN240LAS4
ARWN260LAS4
ARWN120LAS4
ARWN140LAS4
ARWN120LAS4
ARWN120LAS4
3.5 + 3.5
5.8 + 3.5
39
42
127 x 2
127 x 2
280 x 2
280 x 2
(755 × 997 × 500) x 2
(755 × 997 × 500) x 2
19.05(3/4)
19.05(3/4)
34.9(1-3/8)
34.9(1-3/8)
PT 40 + PT 40
PT 40 + PT 40
PT 40 + PT 40
PT 40 + PT 40
20
20