Angled Wall Radiation Shield - Lennox Hearth Products ELITE ME43BK SP Installation And Operation Instructions Manual

43" wood burning fireplaces elite series
Table of Contents

Advertisement

AIR COOLED
STRAPS
Figure 20
RAIN CAP
INSULATED
WALL
FRAME 2" X 4"
Figure 21
18
CHIMNEY AC
BRACE
STORM COLLAR
ROOF SUPPORT
FLASHING
OFFSET SUPPORT
ANGLED INSULATED
WALL RADIATION SHIELD
NOTE: IN COLD FREGIONS IT IS
RECOMMEDNED TO ENCLOSE THE
CHIMNEY IN AN INSULATED CHASE
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

ANGLED WALL RADIATION SHIELD

(RSM+, RSMI30, RSMI45)
When traversing a combustible wall with the
chimney at a 30° or 45° angle, an angled firestop
and/or wall radiation shield must be installed.
Only one is required (Figure 22). Table 6 gives
recommended hole size for installing a wall
ACRS
(RADIATION
radiation shield.
SHIELD)
Note: 45° angle installation for Canada
only.
STRAPS
In cold climate locations, we recommend that
you use the insulated wall radiation shield since
SUPPORT
it will maintain the home's thermal barrier.
RSM+ and RSMI30, RSMI45
Chimney
Angle
Hole Size
Model
ASHT+
14-3/8" x 36-1/2"
30º
8" I.D.
(365mm x 927mm)
Canada
14-3/8" x 24-3/4"
45º
Only
(556mm x 629mm)
S-2100+
16" x 40"
30º
8" I.D.
(406mm x 1016mm)
Canada
16" x 27-1/4"
45º
Only
(406mm x 692mm)
AC
15-1/4" x 38-1/4"
30º
8" I.D.
(365mm x 927mm)
Table 6
INSULATED WALL
DRYWALL
ANGLE WALL RADIATION SHIELD
(INSULATED)
Figure 22