Power Circuit And Cable Requirements - Daikin RXYSQ4P8V1B Installation Manual

Vrv iii-s system air conditioner
Table of Contents

Advertisement

1
2
1
Knock-out hole
2
Burr
3
Packing materials
Use a power wire pipe for the power wiring.
Outside the unit, make sure the low voltage electric
wiring (i.e. for the remote control, between units, etc.)
and the high voltage electric wiring do not pass near
each other, keeping them at least 50 mm apart.
Proximity
may
malfunctions, and breakage.
Be sure to connect the power wiring to the power
wiring terminal block and secure it as described under
"10.4. Connecting power wire and transmission wires"
on page
19.
Inter-unit wiring should be secured as described in
"10.4. Connecting power wire and transmission wires"
on page
19.
Secure the wiring with clamps so that it does not
touch the piping.
Make sure the wiring and the electric box lid do not
stick up above the structure, and close the cover
firmly.

10.5. Power circuit and cable requirements

A power circuit (see table below) must be provided for connection of
the unit. This circuit must be protected with the required safety
devices, i.e. a main switch, a slow blow fuse on the phase and an
earth leakage breaker.
RXYSQ_V1
Phase and
1~ 50 Hz
frequency
Voltage
220-240 V
Recommended
32 A
field fuse
Minimum circuit
27
(*)
amps (MCA)
Transmission line
section
(†)
Wire type
(*) Stated values are maximum values (see electrical data of combination with
indoor units for exact values).
(†) Only in protected pipes, use H07RN-F when protected pipes are not used.
NOTE
Select the power supply cable in accordance with
relevant local and national regulations.
Wire size must comply with the applicable local
and national code.
Specifications for local wiring power cord and
branch wiring are in compliance with IEC60245.
When installing the earth leakage breaker make sure that it is
compatible with the inverter (resistant to high frequency
electrical noise) to avoid unnecessary opening of the earth
leakage breaker.
In connecting the power cable to the power terminal block,
securely clamp the cable as shown in
Installation manual
20
3
cause
electrical
interference,
RXYSQ_Y1
3N~ 50 Hz
380-415 V
16 A
13.5
2
0.75~1.25 mm
H05VV
figure
12.
After finishing the electric work, confirm that each electric
part and terminal inside the electric parts box is connected
securely.
Only for V1: Equipment complying with EN/IEC 61000-3-12
Precautions when laying power wiring
Use round pressure terminals for connections to the power
terminal block.
When none are available, follow the instructions below.
Do not connect wiring of different thicknesses to the
power terminal block. (Slack in the power wiring may
cause abnormal heat.)
When connecting wiring which is the same thickness,
do as shown in the figure below.
1
2
For wiring, use the designated power wire and
connect firmly, then secure to prevent outside
pressure being exerted on the terminal board.
Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will
strip the head and make proper tightening impossible.
Over-tightening the terminal screws may break them.
See the table below for tightening torque for the
terminal screws.
Tightening torque (N•m)
M5 (Power terminal block/ground wire)
M4 (Shielded ground)
M3.5 (Control wiring block)
Field line connection: Control wiring and cool/heat selection
If an excessive force is applied while connecting a cable to
the terminal block on the PC board, the PC board may be
damaged.
For Sky Air or room air conditioner indoor units only: see
1
Cool/heat selector
2
Outdoor unit PC board
3
Take care of the polarity
4
Use the conductor of sheathed wire (2 wire) (no polarity)
5
Terminal board (field supply)
6
BP unit
7
Indoor unit
For VRV indoor units only: see
1
Cool/heat selector
2
Outdoor unit PC board
3
Take care of the polarity
4
Use the conductor of sheathed wire (2 wire) (no polarity)
5
Terminal board (field supply)
(1) European/International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage systems
with input current >16 A and ≤75 A per phase.
(1)
1
Round pressure terminal
2
Power wire
2.39~2.92
1.18~1.44
0.79~0.97
figure
figure
14.
RXYSQ4~6P8V1B+Y1B
VRVIII-S System air conditioner
4PW68122-1 – 02.2011
13.