Power Circuit, Safety Device And Cable Requirements; Wiring Connection Example For Whole System; Leading Wire Procedure - Daikin RXYQ72TATJU Installation Manual

Hide thumbs Also See for RXYQ72TATJU:
Table of Contents

Advertisement

If the ratio exceeds 4%, the unit will shut down and an malfunction
code will be displayed on the indoor remote controller.
• Connect the wire securely using designated wire and fix it with
attached clamp without applying external pressure on the terminal
parts (terminal for power wiring, terminal for transmission wiring
and ground terminal).
• If there exists the possibility of reverse-phase, lose phase, mo-
mentary blackout or the power goes on and off while the product is
operating, attach a reverse-phase protection circuit locally.
Running the product in reverse-phase may break the compressor
and other parts.
9 . 1 . Power circuit, safety device and cable require-
ments
• A power circuit (see the following table) must be provided for con-
nection of the unit. This circuit must be protected with the required
safety devices, i.e. a main switch, a slow blow fuse on each phase.
• When using residual current operated circuit breakers, be sure to
use a high-speed type (0.1 second or less) 200 mA rated residual
operating current.
• Use copper conductors only.
• Use insulated wire for the power cord.
• Select the power supply cable type and size in accordance with
relevant local and national regulations.
Phase and
RXYQ
Voltage
Minimum circuit amp.
frequency
f3, 60 Hz
72TATJU
208/230 V
f3, 60 Hz
96TATJU
208/230 V
f3, 60 Hz
208/230 V
120TATJU
f3, 60 Hz
144TATJU
208/230 V
168TATJU
f3, 60 Hz
208/230 V
f3, 60 Hz
27.6A+36.3A
192TATJU
208/230 V
f3, 60 Hz
216TATJU
208/230 V
36.3A+36.3A
f3, 60 Hz
208/230 V
36.3A+36.3A
240TATJU
f3, 60 Hz
264TATJU
208/230 V
36.3A+55.1A
288TATJU
f3, 60 Hz
208/230 V
55.1A+55.1A
f3, 60 Hz
312TATJU
208/230 V
55.1A+55.1A
336TATJU
f3, 60 Hz
208/230 V
55.1A+55.1A
f3, 60 Hz
208/230 V
36.3A+36.3A+36.3A
360TATJU
f3, 60 Hz
384TATJU
208/230 V
36.3A+36.3A+55.1A
f3, 60 Hz
208/230 V
36.3A+55.1A+55.1A
408TATJU
f3, 60 Hz
72TAYDU
460 V
96TAYDU
f3, 60 Hz
460 V
f3, 60 Hz
120TAYDU
460 V
f3, 60 Hz
144TAYDU
460 V
f3, 60 Hz
460 V
168TAYDU
f3, 60 Hz
192TAYDU
460 V
12.3A+20.6A
216TAYDU
f3, 60 Hz
460 V
20.6A+20.6A
f3, 60 Hz
240TAYDU
460 V
20.6A+20.6A
264TAYDU
f3, 60 Hz
460 V
20.6A+25.9A
f3, 60 Hz
460 V
25.9A+25.9A
288TAYDU
f3, 60 Hz
312TAYDU
460 V
25.9A+25.9A
336TAYDU
f3, 60 Hz
460 V
25.9A+25.9A
f3, 60 Hz
360TAYDU
460 V
20.6A+20.6A+20.6A
384TAYDU
f3, 60 Hz
460 V
20.6A+20.6A+25.9A
f3, 60 Hz
20.6A+25.9A+25.9A
408TAYDU
460 V
19
Maximum
Transmission
overcurrent pro-
line selection
tective device
27.6A
35A
AWG18-16
36.3A
45A
AWG18-16
36.3A
45A
AWG18-16
AWG18-16
55.1A
60A
55.1A
60A
AWG18-16
35A+45A
AWG18-16
45A+45A
AWG18-16
45A+45A
AWG18-16
45A+60A
AWG18-16
60A+60A
AWG18-16
60A+60A
AWG18-16
60A+60A
AWG18-16
45A+45A+45A
AWG18-16
45A+45A+60A
AWG18-16
45A+60A+60A
AWG18-16
AWG18-16
12.3A
20A
20.6A
25A
AWG18-16
20.6A
25A
AWG18-16
25.9A
35A
AWG18-16
25.9A
35A
AWG18-16
20A+25A
AWG18-16
25A+25A
AWG18-16
25A+25A
AWG18-16
25A+35A
AWG18-16
35A+35A
AWG18-16
35A+35A
AWG18-16
35A+35A
AWG18-16
AWG18-16
25A+25A+25A
25A+25A+35A
AWG18-16
25A+35A+35A
AWG18-16

9 .2 . Wiring connection example for whole system

1 1
2
2
4
3
1 Power supply
2 Main switch
3 Fuse or circuit breaker
4 Outdoor unit
5 Remote controller
6 Indoor unit
This image is intended as an example only. Please follow local and
national electrical code.
NOTE
• Make sure the low voltage wiring (i.e. for the remote controller, between
units) and the power wiring do not pass near each other, keeping them at
least 2 in. (51 mm) apart.
Proximity may cause electrical interference, malfunctions, and breakage.
• Be sure to connect the power wiring to the power wiring terminal
block and secure it as described in 9.5. Power wiring connection
procedure.
• Transmission wiring should be secured as described in 9.4. Trans-
mission wiring connection procedure.
• Secure wiring with clamp such as insulation lock ties to avoid con-
tact with piping.
• Shape the wires to prevent the structure such as the control box
cover deforming. And close the cover firmly.
• All field wiring is to be procured on site.

9 .3 . leading wire procedure

• The power wiring and ground wiring are passed out from the power
wiring hole on the front (knock hole).
• The transmission wiring is passed out from the wiring hole (knock
hole) on the front of the unit.
RXYQ72T
1
2
4
3
1
Electric wiring diagram
printed on the back of the control box cover.
2
Knockout hole
3
Power line
4
Transmission line
3
5
6
RXYQ96-168T
1
2
3
4
3P362438-7J
English

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents