Monessen Hearth TPB18 Installation And Operating Instructions Manual page 12

Unvented gas log heater or vented decorative appliance
Table of Contents

Advertisement

CLEARANCES and HEIGHT REQUIREMENTS
Heat resistant material (minimum requirements) with no wooden mantel or other combustible projection:
To install the gas logs into a fireplace with no wooden mantel, shelf or other combustible projection above the fireplace
opening, measure the heat resistant material height, per Figure 5, then see TABLE A.
Heat resistant materials such as slate and marble must be at least 1/2" thick. Sheet metal should not be installed onto
combustible material.
IMPORTANT: If you cannot meet these minimum clearances you must operate the heater with chimney flue damper open.
Refer to "Installing Vented Applications" found on page 18.
HEAT RESISTANT
MATERIAL
MEASUREMENT
12" or more
Hood not required.
8" to less than 12"
Hood not required.
Less than 8"
Extend heat resistant material
to 8" AND install hood. See
Figure 5.
TABLE A - Heat Resistant Material Requirements with no Mantel or Combustible Projection
12
Heat
Resistant
Material
Figure 5 - Measuring Heat Resistant Material
REQUIREMENTS FOR SAFE INSTALLATION
TBP18
Hood not required.
Extend heat resistant material
to 12" OR install hood. See
Figure 5.
Extend heat resistant material
to 8" AND install hood. See
Figure 5. OR, extend heat
resistant material to a height of
at least 12".
Measure
this
distance
Heater in
Fireplace or
Firebox
TBP24
Hood not required.
Extend heat resistant material
to 12" OR install hood. See
Figure 5.
Extend heat resistant material
to 8" AND install hood. See
Figure 5. OR, extend heat
resistant material to a height
of at least 12".
TBP30
70D0004