Flue Options - Potterton Promax FSB 30 HE Installation & Service Instructions Manual

Floor standing fanned flue condensing boiler
Hide thumbs Also See for Promax FSB 30 HE:
Table of Contents

Advertisement

Plume Displacement 70/110 dia Kit
1M Extensions, 45° & 93° bends
are also available - see Section 9.0
NOTE: Horizontal flue pipes should always be installed with a 1.5° fall from the
terminal to allow condensate to run back to the boiler.
This bend is equivalent to
0.5 metre
A
20
© Baxi Heating UK Limited 2010
Horizontal
Flue System Examples
(ii)
(i)
B
(ii)
This bend is equivalent to
0.5 metre
(i)
Total equivalent length =
A+B+2x45°Bends

8.0 Flue Options

8.1
Horizontal Flue Systems
Only a flue approved with the Potterton Promax FSB 30
HE Plus can be used.
(ii)
(i)
Concentric
The maximum equivalent lengths are 4m (horizontal) or
(vertical). Their lengths exclude the standard elbow and
flue/terminal assembly (horizontal) and terminal assembly
(vertical).
Any additional "in line" bends in the flue system must be
taken into consideration. Their equivalent lengths are:
Concentric Pipes:
NOTE: Flue length is measured from point (i) to (ii) as
shown.
IMPORTANT: All flue systems must be securely
supported at least once every metre. Suitable pipe
supports are available as accessories.
45° bend
0.5 m
93° bend
1.0 m