Lennox XC21 Series Unit Information page 38

Lennox xc21 (hfc?410a) series high efficiency residential split?system air conditioner
Hide thumbs Also See for XC21 Series:
Table of Contents

Advertisement

System fault and lockout LED (DS11 / DS14) alarm codes takes precedence over system status LED codes (cooling, heating stages or
defrost/dehumidification). Only the latest active LED fault or lockout alarm code if present will be displayed. If no fault or lockout codes are active, then
system status LEDs are routinely displayed. See notes 1 and 2 in table below for duration of fast / slow flashes and pause.
Air Conditioner
Control LEDs
Thermostat
Thermostat
Thermostat
DS11
DS11
DS14
DS14
Green
Green
Red
Red
Moderate Alert
Off
Slow flash
Critical Alert
Off
On
Moderate Alert
Slow flash
Off
Critical Alert
On
Off
Moderate Alert
Slow flash
On
Critical Alert
Fast flash
On
Critical Alert
OFF
Fast flash
Simultaneous Fast flash
then Pause
Fast simultaneous flashing of DS11, DS13,
DS14 and DS15
1. Pause duration is two (2) seconds.
2. Fast flash duration is 1/2 second. Slow flash duration is one (1) second.
Table 10. Compressor Fault and Lockout LED Codes and Related icomfort Toucht Thermostat Alert Codes
NOTE
See notes 1 and 2 in table below for duration of fast / slow flashes and pause.
Air Conditioner
icomfort
Control LEDs
Toucht
DS15
DS13
Thermostat
Yellow
Red
Display
Moderate/
Off
On
Critical Alert
400
XC21
icomfort
icomfort
icomfort
Toucht
Toucht
Toucht
Condition
Condition
Condition
Display
Display
Display
Low pressure
Code 410
fault
Low pressure
Code 411
switch lockout
High pressure
Code 412
fault
High pressure
Code 413
switch lockout
Discharge line
Code 414
temperature fault
Discharge line
temperature
Code 415
lockout
Moderate /
Discharge sensor
fault
Code 417
Second−stage
None
heat lock−in
OEM mode
Possible
Condition
Cause(s)
Thermostat
Compressor
demand signal
3
internal
Y1 is present, but
overload trip
compressor not
running
Possible
Possible
Possible
Cause(s)
Cause(s)
Cause(s)
1
Restricted air
flow over indoor
or outdoor coil.
2
Improper
1
Remove any blockages or restrictions from coils and/or
refrigerant
fans. Check indoor and outdoor fan motor for proper
charge in
current draws.
system.
2
Check system charge using approach and subcooling
3
Improper
temperatures.
metering device
3
installed or
Check system operating pressures and compare to unit
incorrect
charging charts.
operation of
4
Make sure all pressure switches and sensors have
metering
secure connections to system to prevent refrigerant
device.
leaks or errors in pressure and temperature
4
Incorrect or
measurements.
improper
sensor location
or connection to
system.
This code detects high discharge temperatures. If the discharge line
temperature exceeds a temperature of 279ºF (137ºC) during compressor
operation, the control will de−energize the compressor contactor output (and
the defrost output if active). The compressor will remain off until the discharge
temperature has dropped below 225ºF (107ºC).
The A175 control detects open or short sensor or out of temperature sensor
range. This fault is detected by allowing the unit to run for 90 seconds before
checking sensor resistance. If the sensor resistance is not within range after
90 seconds, the control will raise the alarm.
If the unit is in non−communicating mode and it goes to second stage due to
ambient temperature being below second stage lock−in setting (E48).
Factory Test Mode.
Solution
1
Compressor protector is open.
S
Check for high head pressure
S
Check compressor supply voltage
2
Outdoor unit power disconnect is open.
3
Compressor circuit breaker or fuse(s) is
open.
4
Broken wire or connector is not making
contact.
5
Low or high pressure switch open if present
in the system.
6
Compressor contactor has failed to close.
Page 38
Solution
Solution
Solution
Clearing Status
Clears the error
after current is
sensed in the run
and start winding
for two seconds,
service removed or
power reset.