Inserting The Turbulators; Securing The Boiler Door And Cleaning Cover - Viessmann VITOPLEX 100 Service Instructions Manual

Oil/gas boiler
Table of Contents

Advertisement

Further details regarding the individual steps

Inserting the turbulators

!
Please note
Burner adjustments and specific
system conditions can cause the
turbulators to move forward,
which may result in them being
burnt. This can also lead to dam-
age to the thermal insulation on
the boiler door.
A
10-15°

Securing the boiler door and cleaning cover

Note
On gas burners, remove the gas supply
pipe.
Commissioning, inspection, maintenance
1. Push turbulators A approx. ¼ of
B
2. Bend turbulators approx. 10 - 15°.
3. Push the turbulators into the hot gas
(cont.)
Lock the turbulators in place.
their length into hot gas pipes B.
flues as far as they will go. When
doing this, check the prestress.
Note
Ensure that turbulators cannot easily
be pulled from the hot gas flues.
Danger
Escaping gas leads to a risk of
explosion.
Check all gas connections for
tightness.
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents