Quiet Operation (Cooling Mode/Cooling Area Of Dry Mode) - Panasonic CS-E18NKUA Service Manual

Hide thumbs Also See for CS-E18NKUA:
Table of Contents

Advertisement

Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated above and
the positions of the vane are as Figure 2 below. When the air conditioner is stopped using remote control, the
vane will shift to close position.
12.4.2
Horizontal Airflow
Automatic horizontal airflow direction can be set using remote control; the vane swings left and right within the
angles as stated below. For heating mode operation, the angle of the vane depends on the indoor heat
exchanger temperature as Figure 1 below.
Manual vertical airflow direction can be set using remote control; the angles of the vane are as stated below and
the positions of the vane are as figure below:
12.5

Quiet Operation (Cooling Mode/Cooling Area of Dry Mode)

Purpose
To provide quiet cooling operation compare to normal operation.
o
Control condition
Quiet operation start condition
o
When "Quiet" button at remote control is pressed.
Quiet LED illuminates.
Quiet operation stop condition
o
When one of the following conditions is satisfied, quiet operation stops:
Powerful button is pressed.
Stop by OFF/ON button.
OFF Timer activates.
Quiet button is pressed again.
When quiet operation is stopped, operation is shifted to normal operation with previous setting.
When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs-e24nkuaCu-e18nkuaCu-e24nkua

Table of Contents