Lennox EL195UHE Elite Series Installation Instructions Manual page 33

Elite series gas furnace upflow / horizontal air discharge
Hide thumbs Also See for EL195UHE Elite Series:
Table of Contents

Advertisement

EL195UHE NON−DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
SIZE TERMINATION
PIPE PER TABLE 8.
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
SHEET
METAL TOP
PLATE
INSULATE
TO FORM
SEAL
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver-
tical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illus-
trated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 50
Condensate Piping
This unit is designed for either right- or left-side exit of con-
densate piping in upflow applications. In horizontal applica-
tions, the condensate trap must extend below the unit. An
8" service clearance is required for the condensate trap.
Refer to figures 51 and 52 for condensate trap locations.
Figure 58 shows trap assembly using 1/2" PVC or 3/4"
PVC.
NOTE − If necessary the condensate trap may be installed
up to 5´ away from the furnace. Use PVC pipe to connect
trap to furnace condensate outlet. Piping from furnace
must slope down a minimum of 1/4" per ft. toward trap.
1 − Determine which side condensate piping will exit the
unit, location of trap, field−provided fittings and length of
PVC pipe required to reach available drain.
2 − Use a large flat head screw driver or a 1/2" drive socket
extension and remove plug (figure 51) from the cold
end header box at the appropriate location on the side
of the unit. Install provided 3/4 NPT street elbow fitting
into cold end header box. Use Teflon tape or appropri-
ate pipe dope.
3 − Install the cap over the clean out opening at the base of
the trap. Secure with clamp. See figure 58.
4 − Install drain trap using appropriate PVC fittings, glue
all joints. Glue the provided drain trap as shown in fig-
ure 58. Route the condensate line to an open drain.
Condensate line must maintain a 1/4" downward slope
from the furnace to the drain.
STRAIGHT−CUT OR
ANGLE−CUT IN DIRECTION
OF ROOF SLOPE
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
EXTERIOR
PORTION OF
CHIMNEY
Page 33
CONDENSATE TRAP AND PLUG LOCATIONS
(Unit shown in upflow position)
Trap
(same on
right side)
1−1/2 in.
NOTE − In upflow applications where side return
air filter is installed on same side as the conden-
sate trap, filter rack must be installed beyond
condensate trap or trap must be re−located to
avoid interference.
FIGURE 51
5 − Figures 53 and 54 show the furnace and evaporator
coil using a separate drain. If necessary the conden-
sate line from the furnace and evaporator coil can
drain together. See figures 55, 56 and 57.
Upflow furnace (figure 56) − In upflow furnace applica-
tions the field provided vent must be a minimum 1" to a
maximum 2" length above the condensate drain outlet
connection. Any length above 2" may result in a
flooded heat exchanger if the combined primary drain
line were to become restricted.
Horizontal furnace (figure 57) − In horizontal furnace
applications the field provided vent must be a mini-
mum 4" to a maximum 5" length above the condensate
drain outlet connection. Any length above 5" may re-
sult in a flooded heat exchanger if the combined pri-
mary drain line were to become restricted.
NOTE − In horizontal applications it is recommended to
install a secondary drain pan underneath the unit and
trap assembly.
NOTE − Vinyl tubing may be used for condensate drain.
Tubing must be 1−1/4" OD X 1" ID and should be
attached to the drain on the trap using a hose clamp.
CAUTION
Do not use copper tubing or existing copper conden-
sate lines for drain line.
6 − If unit will be started immediately upon completion of
installation, prime trap per procedure outlined in Unit
Start−Up section.
Plug
(same on left side)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents