Restart Standby - Daikin RZQ71~125B7V3B Service Manual

Sky-air inverter r-410a b series
Table of Contents

Advertisement

General Functionality
1.6

Restart Standby

1
Outline
2
Graph
3
4
5
2–10
To prevent the compressor from frequently turning ON and OFF and allow pressure equalization,
forced thermostat OFF will be conducted for 3 minutes after compressor stopping (compressor guard
timer).
Compressor
Electronic expansion valve
Oudoor unit fan
Restart standby
Thermostat OFF
complete
ON
OFF
OFF
ON
OFF
Residual
operation
For 3 minutes
ESIE04-01
Moves to "Stop" or
"Starting control" after
completion of "Restart
standby".
Part 2 – Functional Description

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents