Ventilated Combustion Air; Termination Requirements For The Provinces Of Alberta And Saskatchewan - International comfort products F9MVT Installation Instructions Manual

Variable speed motor, two?stage ecm motor and single?stage 35” tall, high efficiency condensing gas furnace
Table of Contents

Advertisement

INSTALLATION INSTRUCTIONS
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow the instructions outlined in Locating
the Vent Termination for each appliance being placed
into operation could result in carbon monoxide
poisoning or death.
For all venting configurations for this appliance and
other gas appliances placed into operation for the
structure,
provisions
for
ventilation, and dilution air must be provided in
accordance with:
U.S.A. Installations: Section 9.3 NFPA 54/ANSI
Z223.1 1−2012, Air for Combustion and Ventilation and
applicable provisions of the local building codes.
Canadian
Installations:
CAN/CSA−B149.1−10.
Venting Systems and Air
Supply for Appliances and all authorities having
jurisdiction.

Ventilated Combustion Air

The vent pipe for a Ventilated Combustion Air System must
terminate outdoors. See Figure 60 for references to vent
clearances required by National code authorities. Allowable
vent terminations are shown in Figure 50. The combustion air
pipe terminates in a well−ventilated attic or crawl space. Follow
the clearances as shown in Figure 58 and Figure 59.
The combustion air pipe cannot terminate in attics or crawl
spaces that use ventilation fans designed to operate in the
heating season. If ventilation fans are present in these areas,
the combustion air pipe must terminate outdoors as a Direct
Vent System.
Non−Direct Vent / 1−Pipe System
The vent pipe for a Non Direct Vent (1−pipe) system must
terminate outdoors. See Figure 61 for references to vent
clearances required by National code authorities. Allowable
vent terminations are shown in Figure 50.
A combustion air inlet pipe to the outdoors is not required for a
Non−Direct Vent System. A 12−in. long section of pipe with a
tight radius 2−in. (51 mm) 90 degree elbow is required to be
attached to the furnace. See Figure 46 and Figure 48. This
short inlet air pipe helps to ensure inlet air pipe away from
occupants. An extra elbow and/or five fee (1.5 M) of pipe may
be used to accomplish the sound attenuation function.
Termination Requirements for the
Provinces of Alberta and Saskatchewan
The Provinces of Alberta and Saskatchewan require a
minimum unobstructed distance of 4 ft. (1.2m) from the
foundation to the property line of the adjacent lot for vent
termination of any appliance with an input over 35,000 btuh. If
there is less than 4 ft. (1.2m) of unobstructed distance to the
property line of the adjacent lot, no type of vent termination is
permitted for appliances with inputs greater than 35,000 btuh.
There are no additional restrictions on unobstructed distances
greater than 8 ft. (2.4m). All single, two-pipe and concentric
vents
may
be
used,
providing
manufacturer's requirements in these instructions are adhered
to. Refer to the appropriate Vent Termination section above for
locating the vent termination .
If the unobstructed distance from the foundation to the property
line of the adjacent lot is no less than 4 ft. (1.2m) and no
greater than 8 ft. (2.4m), it will be necessary to re-direct the flue
gas plume. In this situation, a concentric vent kit cannot be
used. A 2-pipe termination (or single pipe termination when
permitted) that re-directs the flue gas away by use of an elbow
or tee, certified to ULC S636 from the adjacent property line
must be used. (See Figure 46 and Figure 48)
440 01 4001 05
adequate
combustion,
Part
8
of
all
other
Code
and
Specifications subject to change without notice.
Gas Furnace: (F/G)9MVT, (F/G)9MXT, (F/G)9MXE
The concentric vent kit currently cannot be modified to attach
an elbow to the vent portion of the rain cap. A tee attached to
the rain cap could potentially direct the flue gas plume toward
the intake air stream and contaminate the incoming combustion
air for the furnace.
Refer to Figure 46 and Figure 48 for terminations approved for
use in Alberta and Saskatchewan.
Figure 46
Tee at Termination Outlet
ABOVE ANTICIPATED
Sample Inlet Air Pipe Connection
Figure 47
for Polypropylene Venting Systems
EXAMPLE FOR
UPFLOW INSTALLATIONS.
MAY BE APPLIED TO
OTHER CONFIGURATIONS.
OPTIONAL TERMINATION
BRACKET FOR 2-PIPE
TERMINATIONS
12 IN. (305 MM) MIN.
SEPARATION BETWEEN
BOTTOM OF COMBUSTION
AIR AND BOTTOM OF VENT.
12-IN. (305 MM)
SNOW LEVEL
A13078A
A12220
41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

G9mvtF9mxeF9mxtG9mxeG9mxt

Table of Contents