Table 12—Gas Rate (cu ft/hr)
SIZE OF TEST DIAL
SECONDS
FOR 1
1
2
REVOLUTION
Cu Ft
Cu Ft
10
360
720
11
327
655
12
300
600
13
277
555
14
257
514
15
240
480
16
225
450
17
212
424
18
200
400
19
189
379
20
180
360
21
171
343
22
164
327
23
157
313
24
150
300
25
144
288
26
138
277
27
133
267
28
129
257
29
124
248
30
120
240
31
116
232
32
113
225
33
109
218
34
106
212
35
103
206
36
100
200
37
97
195
38
95
189
39
92
185
40
90
180
41
88
176
42
86
172
43
84
167
44
82
164
45
80
160
46
78
157
47
76
153
48
75
150
49
73
147
13 for lead color identification. Reconnect original lead on
SPARE terminal.
Follow this same procedure for proper selection of COOL
speed selection.
ADJUST BLOWER OFF DELAY (HEAT MODE)
The blower off delay has 4 adjustable settings from 90 sec to 180
sec. (See Table 14.) The blower off delay jumpers are located on
the furnace control (See Fig. 31). To change the blower off delay
setting, move the jumper from one set of pins on the control to the
pins used for the desired blower off delay. Factory blower off
delay setting is 120 sec.
Table 14—Blower Off Delay Jumper Positions
PINS
1 AND 2
Time (in sec)
90
SIZE OF TEST DIAL
SECONDS
FOR 1
5
1
2
REVOLUTION
Cu Ft
Cu Ft
Cu Ft
1800
50
72
144
1636
51
71
141
1500
52
69
138
1385
53
68
136
1286
54
67
133
1200
55
65
131
1125
56
64
129
1059
57
63
126
1000
58
62
124
947
59
61
122
900
60
60
120
857
62
58
116
818
64
56
112
783
66
54
109
750
68
53
106
720
70
51
103
692
72
50
100
667
74
48
97
643
76
47
95
621
78
46
92
600
80
45
90
581
82
44
88
563
84
43
86
545
86
42
84
529
88
41
82
514
90
40
80
500
92
39
78
486
94
38
76
474
96
38
75
462
98
37
74
450
100
36
72
439
102
35
71
429
104
35
69
419
106
34
68
409
108
33
67
400
110
33
65
391
112
32
64
383
116
31
62
375
120
30
60
367
124
29
58
2 AND 3
3 AND 4
4 AND 5
120
150
180
Table 13—Speed Selector
COLOR
5
Cu Ft
Black
360
355
Yellow (When Present)
346
Blue
340
Red
333
White
327
321
SET THERMOSTAT HEAT ANTICIPATOR
316
When using a nonelectronic thermostat, the thermostat heat
310
anticipator must be set to match the amp draw of the electrical
305
300
components in R-W circuit. Accurate amp draw readings can be
290
obtained at thermostat subbase terminals R and W. Fig. 60
281
illustrates the easy method of obtaining actual amp draw. The amp
273
reading should be taken after blower motor has started and furnace
265
is heating. Connect ammeter wires as shown in Fig. 60. The
257
thermostat anticipator should NOT be in the curcuit while mea-
250
suring current. If thermostat has no subbase, the thermostat must
243
be disconnected from R and W wires during current measurement.
237
See thermostat manufacturer's instructions for adjusting heat
231
anticipator and for varying heating cycle length.
225
For an electronic thermostat, set cycle rate for 3 cycles per hour.
220
Step 5—Check Safety Controls
214
209
This section covers the safety controls that must be checked before
205
the installation is complete. The flame sensor, gas valve, and
200
pressure switch were all checked in the Start-up procedure section
196
as part of normal operation.
192
CHECK PRIMARY LIMIT CONTROL
188
This control shuts off gas control system and energizes air-
184
circulating blower motor if furnace overheats. Recommended
180
method of checking this limit control is to gradually block off
178
return air after furnace has been operating for a period of at least
173
5 minutes. As soon as limit control has shut off burners, return-air
170
opening should be unblocked to permit normal air circulation. By
167
using this method to check limit control, it can be established that
164
161
limit is functioning properly and operates if there is a restricted
155
return-air duct or motor failure. If limit control does not function
150
during this test, cause must be determined and corrected.
145
CHECK PRESSURE SWITCH
This control proves operation of draft inducer. Check switch
operation as follows:
1. Turn off 115-v power to furnace.
2. Remove outer furnace door and disconnect inducer motor
from wire harness.
3. Turn on 115-v power to furnace.
4. Set thermostat to "call for heat" and wait 1 minute. When
pressure switch is functioning properly, hot surface igniter
should NOT glow, and control status code LED flashes a
Status Code 31. If hot surface igniter glows when inducer
motor is disconnected, shut furnace down immediately. De-
termine reason pressure switch did not function properly and
correct condition.
5. Turn off 115-v power to furnace.
6. Reconnect inducer motor leads, reinstall main furnace door,
and turn on 115-v power supply.
Step 6—Checklist
1. Put away tools and instruments. Clean up debris.
2. Verify flame-rollout manual reset switch has continuity.
48
FACTORY-
SPEED
SHIPPED
CONNECTION
High
Cool
Medium High
Spare
Medium Low
Heat
Low
Fan
Common