Rheem RGRK SERIES Installation Instructions Manual page 31

For upflow and downflow/horizontal high efficiency condensing two-stage gas furnaces
Table of Contents

Advertisement

(-)XGY-G02 Side Wall Vent
This termination for horizontal venting
only.
IMPORTANT: Do not install on the
prevailing winter wind side of the
structure. Observe same clearance
specified for horizontal, standard
termination.
NOTE: Multi-venting-No common
venting.
FIGURE 25
VENT KIT INSTALLATION OPTIONS
FIGURE 26
TYPICAL INSTALLATIONS
NOTE: Install the vent and air intake
piping into the vent plate openings.
Seal all gaps between the pipes and
wall. Be Sure To Use Silicone Sealant
to seal the vent pipe to the vent cap
to permit field disassembly for annual
inspection and cleaning. Also seal all
pipe penetrations in wall. To prevent
possibility of condensate freeze-up or
recirculation, do not install vent kits
one above the other.
EXHAUST
AIR
INTAKE
NOTE: The vent illustration in Figure
26 can be used for non-direct vent
terminations also.
31