6.1.2. Diagnostic code for indoor unit
Flash times of
Flash times of
Timing LED(or
Running LED(or
indoor PCB
indoor PCB
LED4)
LED3)
0
1
0
2
0
4
0
7
0
8
0
12
0
13
0
14
0
16
2
1
2
2
2
4
2
5
2
7
2
8
2
9
3
0
3
1
3
2
3
3
3
5
3
6
3
7
3
8
3
9
4
3
4
4
4
7
4
8
4
9
5
8
5
9
6
3
6
4
1. . For the indoor failu ,only running LED ON remote receiver will indicate.
2. . For the outdoor failu ,timer LED and running LED will indicate.timer LED of remote receiver stands for ten's place,and running LED
stands for one's place.timer LED will flash firstly,2 seconds later,running LED will flash too. Afer that,4 seconds later,they will flash in
turns again.Flash times equals to the failure code of outdoor plus
20.For example,failure code of outdoor is 2,the indoor unit should display 22.As a result,timer LED flashes twice firstly,then running LED
flashes twice.
3.
To get much more details of outdoor unit failure,Please refer to the the outdoor unit trouble shooting list
Failure
Failure code(from
code(from panel
wired controller)
controller )
01
E1
02
E2
04
F8
07
E9
NO EEROR
CODE DISPLAY
E8
0C
E0
OD
EF
0E
/
10
F3
15
/
16
/
18
/
19
/
1B
/
1C
/
1D
/
1E
/
1F
/
20
/
21
/
23
/
24
/
25
/
26
/
27
/
2B
/
2C
/
2F
/
30
/
31
/
3A
/
3B
/
3F
/
40
/
trouble shooting
Temperature sensor
Ta faulty
Temperature sensor
Te faulty
EEPROM WRONG
Abnormal
communication
between indoor and
outdoor units
Abnormal
communication
between indoor wired
controller and indoor
unit PCB
Drainage system
abnormal
Zero cross sigal wrong Zero cross sigal detected wrong
Indoor unit DC fan
motor abnormal
Indoor mode abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
Outdoor unit abnormal
124
Possible reasons
Sensor disconected,or broken,or
at wrong position,or short circuit
Sensor disconected,or broken,or
at wrong position,or short circuit
Faulty indoor unit PCB
Wrong connection,or the wires be
disconected,or wrong address
setting of indoor unit,or faulty power
supply or faulty PCB
Abnormal communication between
indoor wired controller and indoor unit
PCB
Pump motor disconnected,or at
wrong position,or the float switch
broken down,or the float switch
disconected,or at wrong position.
DC fan motor disconnected,or DC fan
motor broken,or circuit
broken
Different from outdoor unit mode
Refer to the outdoor unit trouble
shooting
list