Weil-McLain WM97+ Product Manual page 32

Companion water heater for wm97+ gas-fired boilers
Hide thumbs Also See for WM97+:
Table of Contents

Advertisement

CWH
companion water heater
Troubleshooting
5 Check for air in the system
An air-bound water heater or boiler will not circulate system water properly, resulting in a lack of heat
transfer.
Air can be trapped in piping loop sections, the tank coil or the flexible water lines between the boiler and
CWH.
Connect a drainage hose to the boiler supply piping purge valve (shown in WM97+ manual suggested
piping).
Close the WM97+ internal by-pass valve (be sure to return to normal position after purging).
Allow water to flow into the boiler return line from the make-up water connection to the system.
Allow water to flow until air bubbles no longer appear in the discharge from the drainage hose.
Remove drainage hose and return by-pass valve to the normal position.
6 Clean the boiler water system.
A dirty boiler system can cause deposits to form on the water heater coil. This insulates the coil, reducing
the heat transfer.
Clean the boiler system per the boiler manufacturer's instructions.
Install a strainer in the boiler piping on older installations or for systems likely to carry sediment.
7 Check tank temperature setting
Follow directions in this manual to navigate to the tank temperature setting menu.
Increase the setting if necessary.
Also check the operating mode. Change mode to "High-max performance" if water heater is set to another
mode.
8 Check DHW circulator speed
The CWH is supplied with a 3-speed circulator. The speed switch on the circulator must be set to:
Speed 1
Speed 3
32
— Product Manual
(continued)
Insufficient hot water
for WM97+70 or 110 boilers.
for WM97+155 boilers.
(continued)
Part number 635-500-156/0113

Advertisement

Table of Contents
loading

Table of Contents