CWH
companion water heater
Troubleshooting
1 Undersized water heater?
•
There are many methods of sizing various applications, i.e. ASHRAE sizing tables or ASPE domestic water
heating design manual.
•
Confirm the water demand required for the application.
•
Confirm the flow rates of the fixtures.
•
For example, was the tank sized for shower heads at 2.0 gpm, while the actual heads are 5.0 gpm?
•
Use a bucket and a stopwatch to determine fixture flow rates.
•
Evaluate the hot water usage pattern for a day.
•
Is the peak demand unusually high for the application?
•
Has the demand for domestic hot water changed since the system was installed?
•
A bathroom remodeling project — new shower fixtures or a whirlpool tub would substantially change
the domestic water demand.
•
New appliance added, such as a dishwasher or clothes washer?
2 Boiler system improperly sized?
•
Can the boiler provide the required output to meet the domestic water load?
•
Have a qualified service technician determine the domestic water heating load.
•
Compare to the capacities listed at the end of this manual to ensure the WM97+ boiler and CWH
water heater are correctly sized.
3 Check component parts.
•
Is the WM97+ control set properly and operating correctly?
•
Review WM97+ Boiler manual and this manual to check control settings.
•
If water heater control is set to "SCHEDULE," check whether the problem is occurring during times
when the operating mode is set to Economy.
•
Try changing operating mode to "High-performance."
•
During a call for heat by the water heater, does the CWH circulator begin pumping, does the boiler fire?
Check all components in the system to ensure they are properly functioning.
4 Check boiler operating temperatures.
•
If possible, increase the boiler operating temperature to 180°F or 190°F or increase tank storage tempera-
ture. Read the boiler manual and this manual for adjustment instructions and WARNINGS.
•
Maintain a minimal temperature in the boiler during non-heating seasons.
•
A boiler typically has a higher standby loss than the indirect water heater.
•
After a long standby period, the colder boiler may absorb the stored energy within the water heater
during the initial call for heat.