Chapter 2
Rack Installation Specifications
2.2
Installable Racks
Connections in the same rack are omitted in the above figure.
•
•
The number of extension cables required is determined by the total number of installed drive enclo-
sures.
2.2
Installable Racks
This section explains the racks in which the ETERNUS DX can be installed.
2.2.1
Fujitsu Racks
The ETERNUS DX can be installed in a Fujitsu 19-inch rack. For information about whether the ETERNUS DX
can be installed in an EOLed rack or not, contact your sales representative.
2.2.2
Non-Fujitsu Racks
The ETERNUS DX storage systems are developed and their operation is guaranteed on the assumption that
they are installed in Fujitsu 19-inch racks. Since the ETERNUS DX cannot be tested (for cooling and strength)
in non-Fujitsu 19-inch racks, the operations of ETERNUS DX storage systems cannot be guaranteed. Any
problem that may occur by installing the ETERNUS DX in non-Fujitsu racks is not covered by the warranty.
If the ETERNUS DX needs to be installed in a non-Fujitsu rack, the following conditions must be satisfied.
■
Rack Specifications
Use the rack mount kit supplied with the product to install the ETERNUS DX in the rack. The rack specifica-
tions must satisfy the conditions listed below. For rack specifications, refer to the manual for the rack that is
used.
Pitch for mounting holes
•
EIA Standard Universal pitch
Size for mounting holes
•
The size of the square holes must be 9mm or more.
Load bearing capacity
•
The load bearing capacity must be equal to or larger than the total weight of the ETERNUS DX.
Unit Installation Area
•
The dimensions of the area shown in
FUJITSU Storage ETERNUS DX500 S3/DX600 S3 Disk storage system Site Planning Guide
Figure 2.10
must match the conditions described in
48
Copyright 2014 FUJITSU LIMITED
Table
2.3.