Empire Comfort Systems DVP42DP31N-2 Installation Instructions And Owner's Manual page 20

Direct vent zero clearance gas fireplace heater
Table of Contents

Advertisement

VENTING FIREPLACE - TOP (continued)
Minimum hole location dimensions for through the wall hori-
zontal installations with 90 degree elbow off top of fireplace.
HARD ELBOW DIMENSIONS
"A"
43-1/2"
(1105mm)
(127mm)
FLEX PIPE 90 DEGREE BEND
"A"
46"
(1143mm)
(127mm)
Positioning the Fireplace
Determine the exact position of the appliance so the direct vent
termination will be centered (if possible) between two studs. This
will avoid any extra framing. All vent kit pipes should be assembled
on the unit after the unit is moved into the final position.
Cutting the Hole
After the fireplace has been positioned in its permanent location,
the hole through the exterior wall of the house can be cut. This hole
must be 12" (305mm) high x 10" (254mm) wide with its center line
determined by the amount of vertical rise and horizontal run of the
termination. See Figure 29. When locating the hole it must be noted
that the bottom of the cap must be 12" (305mm) above the ground
level, and top of the cap must be no less than 18" (457mm) below a
combustible projection, and no closer than 9" (229mm) to any wall
running parallel to vent termination. See Figure 30.
Page 20
Figure 29
"B"
"C"
5"
7"
(178mm)
"B"
"C"
5"
7" (178mm)
Figure 30
Figure 31
31457-1-0513

Advertisement

Table of Contents
loading

Table of Contents