APPLICATION
PVC,CPVC or ABS
SCH. 40 Pipe Size
Model M3RL 060
Model M3RL 080
MAXIMUM
DIRECT VENT, DUAL
PIPE LENGTH (ft.)*
Inlet/Outlet
3"
3"
50
50
50
50
*NOTES
1.
Subtract
3.5 ft. for each additional
3" 90 degree
elbow.
2.
Two45 degree elbows are equivalent
to one 90 degree elbow
3.
One short
radius
elbow
is equivalent
to two long
radius
elbows.
4.
Do not include termination
elbows in calculation
of vent length
5.
This table is applicable
for elevations
from sea level to 400C
ft. For higher elevations,
decrease
vent pipe lengths by 8% pel
1000ft.
of altitude.
6.
Onlythe
above pipe materialsare
approved
for usewith
these
condensing
furnaces.
Table 6. Vent Table
[]
VENT
TERMINAL
(_
AiR
SUPPLY
INLET
[]
AREA
WHERE
TERMINAL
IS NOT
PERMITTED
A = Clearance above grade, veranda, porch,
deck, balcony, or snow accumaulation
level
B -- Clearance to window or door that may be
opened
C = Clearance to permanently
closed window
D = Vertical clearance to ventilated
soffit
located above the terminal within a
horizontal distance of 2 feet (61 cm) from
the center line of the terminal
E = Clearance to unventilated
soffit
F = Clearance to outside corner
G = Clearance to inside corner
H = Clearance to each side of center line
extended above meter/regulator
assembly
I =
Clearance to service regulator vent outlet
J = Clearance to nonmechanical
air supply inlet
to building or the combustion
air inlet to any
other appliance
Canadian
Installations
1
12 inches (30 cm)
6 inches (15 cm) for appliances
< 10,000
Btuh (3 kW), 12 inches (30 cm)for
appliances
> 10,000 Btuh (3 kW) and <
100,00 Btuh (30 kW), 36 inches (91 cm)for
appliances
>100,00 Btuh (30 kW)
3 feet (91 cm) within a height 15 feet
above the meter/regulator
assembly
3 feet (1.83 m)
6 inches (15 cm) for appliances
< 10,000
Btuh (3 kW), 12 inches (30 cm)for
appliances
> 10,000 Btuh (3 kW) and <
100,00 Btuh (30 kW), 36 inches (91 cm)for
appliances
>100,00 Btuh (30 kW)
6 feet (1.83 m)
US Installations
2
12 inches (30 cm)
6 inches (15 cm) for appliances
< 10,000
Btuh (3 kW), 9 inches (23 cm) for
appliances
> 10,000 Btuh (3 kW) and <
50,000 Btuh (15 kW), 12 inches (30 cm) foi
appliances
> 50,000 Btuh (15 kW)
K = Clearance to a mechanical
air supply inlet
L -- Clearance above paved sidewalk or paved
7 feet (2.13 m) 1"
,
driveway located on public property
M -- Clearance under veranda, porch deck, or
12 inches (30 cm) $
,
balcony
6 inches (15 cm)for
appliances
< 10,000
Btuh (3 kW), 9 inches (23 cm) for
appliances
> 10,000 Btuh (3 kW) and <
50,000 Btuh (15 kW), 12 inches (30 cm) foi
appliances
> 50,000 Btuh (15 kW)
3 feet (91 cm) above if within 10 feet (3 m)
horizontally
In accordance
with
the
current
CSA
B149.1
Natural
Gas
and
Propane
Installation
Code
2
In accordance
with
the
current
ANSI
Z223.1
/ NFPA
54
National
Fuel
Gas
Code
1" A vent
shall
not terminate
directly
above
a sidewalk
or paved
driveway
that
is located
between
two
single
family
dwellings
and
serves
both
dwellings.
$
Permitted
only
if veranda,
porch,
deck,
or balcony
is fully
open
on a minimum
of two sides
beneath
the floor.
For
clearances
not
specified
in ANSI
Z223.1
/ NFPA
54
or CSA
B149.1,
the following
statement
shall
be
included:
"Clearance
in accordance
with
local
installation
codes,
and the
requirements
of the
gas
supplier
and
the
manufacturer's
installation
instructions."
Figure
15. Vent Termination
Clearances
for Direct Vent Furnaces
15