Hydraulic Connection Of The Heating Circuit - Potterton NXR5i Installation And Service Manual

Fuel oil/ gas boilers nxr5i series
Hide thumbs Also See for NXR5i:
Table of Contents

Advertisement

4.4.3

Hydraulic connection of the heating circuit

Water flow in the boiler
The water flow in the boiler when the burner is operating must
correspond with the following formulae:
- Nominal water flow Qn = 0.86 Pn/20.
- Minimum flow Qmin = 0.86 Pn/45 (this flow also corresponds with
the minimum recycle flow in the boiler).
- Maximum water flow Qmax = 0.86 Pn/5.
3
Qn = flow in m
/h
Pn = Nominal output (full boiler output) in kW.
Connect the flow controller to the terminal blocks UV in the
control panel KSF CE.
Connect the flow switch to Q between terminals SK1 and SK2
on the KSF ISR control panel.
Operation in cascade
After stopping the burner:
- Timeout required before the order to close a 2 way valve: 3 min.
- Switch a possible shunt pump (located between the boiler and a
butterfly valve) off via the end of run contact of the butterfly valve.
Minimum safety valve flowrate as a function of maximum boiler nominal output
Minimum relieving capacity
Maximum gross boiler output
Unit
(a) = kW
(b) = lb/h
(c) = MBtu/h
(d) = Kg/h
16
Operation with 2-stage burner
- The water temperature in the boiler is maintained at 50°C or more;
The first stage must be set to a minimum of 30% of the nominal
stage.
- Operation at modulated low temperature (minimum outlet
temperature: 40°C); The first stage must be set to a minimum of
50% of the nominal stage.
Refer to the installation and service manual for the KSF CE
control panel.
Operation with modulating burner
- The water temperature in the boiler is maintained at 50°C or more:
The burner can modulate down to 30% of the nominal stage.
- Operation at modulated low temperature (minimum outlet
temperature: 40°C); The burner can modulate down to 50% of the
nominal stage.
Refer to the installation and service manual for the KSF ISR
control panel.
Example:
Maximum boiler nominal output is 800 kW.
Minimum safety valve flowrate must be 2600 Kg/h.
There must be no total or partial closing mechanism
between the boiler and the safety valves (France: DTU -
65.11, § 4.22 - NF P 52-203).
NXR5i
17/04/2012 - 300029103-001-01