Controller - Mitsubishi Electric Mr.SLIM PCA-RP50KAQ Service Manual

Series pca split-type, heat pump air conditioners
Hide thumbs Also See for Mr.SLIM PCA-RP50KAQ:
Table of Contents

Advertisement

OPERATING PROCEDURE
7. Removing the vane motor
(1) Remove the air intake. (See Figure 1, 2)
(2) Remove the right side panel. (See Figure 3, 4)
(3) Remove the connector of vane motor.
(4) Remove 2 screws of vane motor cover , then remove
vane motor.
8. Removing the under panel
(1) Remove the air intake grille. (See Figure 1, 2)
(2) Remove the left and right side panels. (See Figure 3, 4)
(3) Remove the beam. (See Photo 1)
(4) Remove the electrical cover. (See Photo 1)
(5) Pull the electrical box downward. (See Photo 2)
(6) (Wireless remote controller receiver type only)
Disconnect the connector CNB from the PCB for wire-
less remote controller and remove the clamp and strap
for wires.
(7) Remove 8 screws from the under panel.
(8) Move the under panel forward by about 10mm and
remove the under panel.
9. Removing the drain pan
(1) Remove the air intake grille. (See Figure 1,2)
(2) Remove the side panel (right and left). (See Figure 3, 4)
(3) Remove the under panel. (See Photo 14)
Remove the screws of the right and left side drain pan.
(See Photo 15)
(4) Remove 2 insulation in center of the drain pan, and after
removing 2 screws with washer, remove the drain pan.
(See Photo 16,17)
(Note)
Please be aware that there might be some drainage left in
the drain pan when you remove the drain pan.
OCH491C
Photo 17
Screw with
washer
(2 locations)
PHOTOS & ILLUSTRATIONS
Photo 13
Vane motor and cover
Screws
Photo 14
Under panel fixing
screws
Photo 15
Drain pan fixing
screws
(left and right
each 1 screw)
Photo 16
Vane
44
Connector
Pipe cover fixing screws
Drain pan
Insulations

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mr.slim pca-rp60kaqMr.slim pca-rp71kaqMr.slim pca-rp100kaqMr.slim pca-rp125kaqMr.slim pca-rp140kaqMr.slim pca-rp35kaq ... Show all

Table of Contents