SETTING UNIT NOMINAL CAPACITY CODE
In a icomfortt enabled system, if the icomfort Toucht
thermostat is displaying either of the following alert codes,
then the outdoor unit normal capacity will need to be set
using the procedures outlined in figure 26.
START
Set room thermostat
to OFF
Go to air conditioner
control terminal strip
Remove R wire
from air conditioner
control (24 volt AC
power)
®
icomfort
enabled
Remove control wires
from i+ and i− terminals
Place jumper on
FIELD TEST
(E33 pins)
Connect R wire to air
conditioner control (24
volt AC power)
Status LED lights DS11
and DS14 will blink and
then on continuously.
The lights must be on
continuously to proceed
to the next step.
Remove jumper
from FIELD
TEST (E33 pins)
between 2 to 10
seconds.
Figure 26. Air Conditioner Control (A175) Unit Nominal Capacity Code Configuration
®
Non − icomfort
enabled
Remove
control wire from Y1
terminal
Place jumper on FIELD
TEST (E33 pins) within 2 to
10 seconds after removal
The air conditioner control´s DS11 and
DS14 LEDs will start blinking the Unit
Nominal Code at three (3) second
intervals starting at 1−ton through to
6−ton. If a code is not selected, the air
conditioner control will cycle one more
time through the codes before defaulting
back to the idle mode (simultaneous
slow flash).
Long blink ON red LED (DS14) to
indicate tonnage and solid ON green
LED (DS11) to indicate ½ tonnage.
1. Alert Code 34, Must Program Unit Capacity for
Outdoor Unit.
2. Alert Code 313, Indoor and Outdoor Unit Capacity
Mismatch.
DS14 (Red)
DS11 (Green)
Field Test
(E33)
DS12
Communicating
Status Indicator
Sensor harness
must be attached
to air conditioner
control.
When the required Unit Capacity Code
is displaying on the LEDs, remove
FIELD TEST jumper from pins (E33).
LEDs will continue to display the
selected unit capacity code for two (2) minutes
before defaulting back to the idle mode
{simultaneous slow flash}, or until the 24 volt
power is cycled to the air conditioner control.
Page 47
FINISH
Connect R wire to air
conditioner control (24
volt AC power)
Reconnect any control
wiring previously
removed.
Remove R wire from
air conditioner control
(24 volt AC power)
DS11
Green
DS14
Model
Size
LED
Red LED
−012
1−ton
OFF
1 long flash
−018
1.5−ton
ON
1 long flash
−024
2−ton
OFF
2 long flashes
−030
2.5−ton
2 long flashes
ON
−036
3−ton
OFF
3 long flashes
−042
3.5−ton
ON
3 long flashes
−048
4−ton
4 long flashes
OFF
−054
4.5−ton
4 long flashes
ON
−060
5−ton
OFF
5 long flashes
−066
5.5−ton
ON
5 long flashes
−072
6.0−ton
6 long flashes
OFF
XC17