Unit Dimensions - Lennox XC17 Series Unit Information

Xc17 (hfc−410a) series units
Table of Contents

Advertisement

Maximum Over−
Model Number
current Protection
XC17−060−230−01
XC17−060−230−02
XC17−060−230−03
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
Unit Dimensions − Inches (mm) and Parts Arrangement
39.40"
(1003)
SIDE VIEW
XC17
208/230V−60 Hz−1 Ph
Unit
Minimum
Circuity
1
2
(amps)
Ampacity
60
35.0
60
35.0
50
33.3
DISCHARGE AIR
SUCTION LINE
INLET
LIQUID
LINE
INLET
UNIT SUPPORT
FEET
16−7/8
(429)
8−3/4
(222)
3−1/8
(79)
BASE WITH ELONGATED LEGS
Compressor
Locked
Rated Load
Rotor Amps
Amps (RLA)
(LRA)
26.4
134.0
26.4
134.0
25.0
134.0
ELECTRICAL INLETS
[−024] 41" (1040)
[−030 THROUGH
−060] 47" (1194)
18.60"
(470)
8.00" (203)
1 (25)
30−3/4
(781)
Page 4
Condenser Fan
Motor HP
Nominal RPM
1/4
675
1/4
675
1/4
675
35.50"
(902)
ACCESS VIEW
26−7/8
(683)
3−3/4 (95)
4−5/8
(117)
Full Load
Amps (FLA)
2.0
2.0
2.0

Advertisement

Table of Contents
loading

Table of Contents