Model Nomenclature - Heat Controller HBH Series Installation, Operation & Maintenance Manual

Commercial horizontal packaged water source heat pump 6-10 tons hbh series;
Hide thumbs Also See for HBH Series:
Table of Contents

Advertisement

HBH Large Compact Horizontal Units
Heat Controller, Inc.
Entering Water Temperature Range: 20 - 120° F (-6. 7 - 48.9° C)

Model Nomenclature

Horizontal Sizes 072 - 120
HBH Large Model Structure
Basic Unit Description:
The basic unit price includes sealed heat pump refrigerant circuit and
air handler within cabinetry, filter, and a factory installed hanger kit on
horizontal units.
• Cabinetry - Compact design - galvanized steel construction -
FPT water connections, high and low voltage knockouts - filter
and filter brackets. All horizontal units have field convertible discharge
air patterns, no extra parts required.
• Standard Controls - CXM Controller, loss of charge switch, high
pressure switch, water coil low temperature cutout, lockout safety
circuit reset at thermostat or disconnect, LED fault indication,
five minute anti-short cycle, random start, high and low voltage
protection, condensate overflow protection, dry contact for alarm.
• Compressor - High efficiency scroll compressor - overload
protected.
• Refrigerant Circuit - Dual refrigerant circuit. Thermostatic
expansion valve's for refrigerant metering, copper tubing
interconnecting all components - sealed & tested non-ozone
depleting, HFC-410A refrigerant circuit with high and low-side
R-410A refrigerant circuit with high and low-side
Schrader ports.
Heat Controller OEM Price List
HBH SERIES
3
• Reversing Valve - 4-way, pilot operated, solenoid activated in
cooling.
• Water to Refrigerant Coil - Tube-in-tube, convoluted copper inner
water tube.
• Refrigerant to Air Coil - Lanced aluminum fins on rifled copper
tubes.
• Blower Motor - Belt drive with adjustable sheave, single blower and
single blower motor.
• Application - Units can be applied in WLHP, GWHP or GLHP
applications.
• Field Connections - For supply, return and condensate can be made
on either side (plug opposite side). Condensate connection on end
opposite compressor end.
Page 15
2
IOM Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hbh072Hbh096Hbh120

Table of Contents