[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No.
1
Gauge manifold
2
Charge hose
3
Electronic scale
4
Gas leak detector
5
Adaptor for reverse flow check
6
Refrigerant charge base
7
Refrigerant cylinder
8
Refrigerant recovery equipment
3
PART NAMES AND FUNCTIONS
● Indoor Unit
Vane
Gravimeter
Tool name
Air outlet
· Only for R410A
· Use the existing fitting specifications . (UNF1/2)
· Use high-tension side pressure of 5.3MPa·G or over.
· Only for R410A
· Use pressure performance of 5.09MPa·G or over.
· Use the detector for R134a, R407C or R410A.
· Attach on vacuum pump.
· Only for R410A
· Top of cylinder (Pink)
· Cylinder with syphon
Louver
Filter
(Inside of Air intake)
Air intake
4
Unit
Specifications
—
—
—