Description
Infloor's programmable thermostat has three temperature control
modes:
A mode:
controls the ambient air temperature
F mode:
controls the floor temperature using an
external temperature sensor
AF mode:
controls the ambient air temperature
maintains the floor temperature within desired
limits using an external temperature sensor
1
On/Standby switch
2
and GFCI reset
Appears when the
setpoint is displayed
Day and time
settings
Percentage of
3
heating time
Program button
Program
clear button
Mode selection /
program exit
Backlight button
1
Place the switch in Standby to cut power to the heater when not in use (e.g., in the sum-
mer). This will not affect the time and temperature settings.
2
If your thermostat is installed on a power base equipped with a ground fault protection,
to reset the ground fault protection, switch the thermostat to Standby and back to On.
3
The thermostat displays the percentage of heating time required to maintain the desired
temperature. For example,
is displayed when heating is activated 40 percent of the
time.
Display
% of heating time
1 to 24% 25 to 49% 50 to 74% 75 to 99%
4
GFI appears when the ground fault protection has tripped.
Configuration
Some thermostat configurations can be modified via
switches on the back of the faceplate (control module).
Default (factory) settings are inside the gray cells.
#
Configurations
1
Display format
a
2
Early Start
3
Temperature control mode
a.
Early Start can be used in Automatic mode only. When this function is enabled, the
thermostat calculates the optimal time to start heating in order to obtain the desired
temperature by the set time. The thermostat re-assesses the start time daily based
on the previous day's results.
NOTE: If you wish to use only 2 periods, set periods "1 and 4" or periods "2 and 3".
Early Start will not work if you set periods "1 and 2" or periods "3 and 4"
b.
To select the F mode, place the switch in the F position. To select the AF mode,
place the switch in the AF position and ensure that the remote temperature sensor
is connected to the thermostat. To select the A mode, place the switch in the AF
position and ensure that the remote temperature sensor is NOT connected to the
thermostat.
Installation
Refer to the installation
instructions of the power
base.
Insert the tabs at the top of
the control module in the slots
at the top of the power base.
Secure the control module
using the captive screw
underneath the base.
NOTE: Keep the thermostat's air vents clean and unobstructed at all times.
TH115 A/F/AF
Time and day display
Temperature display
Mode display
Preset temperature
indicator
Ground fault indicator
Temperature control
mode indicator
Temperature
preset buttons
Period display
Temperature
adjustment buttons
100%
UP
DN
°F / 12 h
°C / 24 h
Enable
Disable
b
F
AF
Air vents
Control module
Air vents
Power base
1.

Clock and Day Setting

Press the Hour button to set the hour.
Set the Min button to set the minutes.
Set the Day button to set the day.
Press Mode/Ret to exit.
Daylight Savings Time
The thermostat can automatically re-adjust its clock at Daylight Sav-
ings Time changeover. When this function is enabled (On), the ther-
mostat switches to Daylight Savings Time on the second Sunday of
March and to normal time on the first Sunday of November.
NOTE: The function is disabled (default setting) when the clock loses
its setting.
Press the Day button (3 seconds) until DLS appears
on the screen.
Press the
to toggle between On (enabled) and Off
4
(disabled).
Press the Day button briefly. The year setting is dis-
played.
Press the
to set the current year.
Press the Day button briefly. The month setting is dis-
played.
Press the
to set the current month.
Press the Day button briefly. The date setting is dis-
played.
Press the
to set the current date.
Press Mode/Ret to exit.
Backlight
The display illuminates for 12 seconds when the backlight button is
pressed.
When either of the
2.
for 12 seconds. The setpoint temperature appears for 5 seconds,
then the actual (measured) temperature is displayed.

Temperature Adjustment

6.1

Setpoint Temperature

The thermostat normally displays the actual (measured) temperature.
To view the setpoint, press one of the
will appear for the next 5 seconds.
To change the setpoint, press one of the
temperature is displayed. To scroll faster, press and hold the button.
6.2

Preset Temperatures

The thermostat has 3 preset temperatures:
Comfort temperature
Economy temperature
Vacation temperature
To use a preset temperature, briefly press the corresponding button.
3.
The corresponding icon
The following table shows the intended use and the default setting of
each of the preset temperatures.
Icon
Intended use
Comfort
(when at home)
Economy
(when asleep or away from home)
Vacation
(during prolonged absence)
To store a preset temperature:
Set the desired temperature using the
Press and hold the corresponding button until the corresponding
icon is displayed.
TH115 A/F/AF

Programmable Thermostat

buttons is pressed, the display also illuminates
buttons once. The setpoint
buttons until the desired
,
or
will be displayed.
A/AF modes
21 °C (70 °F)
17 °C (63 °F)
10 °C (50 °F)
buttons.
400-115-039-C
11/4/07

User Guide

4.
5.
6.
F mode
28 °C (82 °F)
20 °C (68 °F)
10 °C (50 °F)
1/2Infloor's

Advertisement

loading

Summary of Contents for Aube Technologies TH115 A

  • Page 1: User Guide

    TH115 A/F/AF User Guide Programmable Thermostat Description Clock and Day Setting Infloor's programmable thermostat has three temperature control Press the Hour button to set the hour. modes: Set the Min button to set the minutes. A mode: controls the ambient air temperature Set the Day button to set the day.
  • Page 2: Vacation Mode

    This warranty does not cover removal or reinstallation costs. This warranty shall not apply if it is shown by Infloor that the defect or malfunction was caused by dam- Period Setting age which occurred while the product was in the possession of a consumer.
  • Page 3: Installation Instructions

    PB112B Installation Instructions For models: 120GA / 120GB / 240GA / 240GB Insert the floor sensor cable through one of the two openings on Applications the base and connect the sensor wires to terminals 1 and 2 (no polarity). This power base has been designed for floor heating applications. It Position the sensor cable such that it does not come in contact has ground fault protection (GFCI or EGFPD...
  • Page 4: Technical Specifications

    Ground Fault Protection 5.1 Description The power base protects against risks TEST button/light of electrocution caused by leakage current. If the leakage current exceeds 5 mA or 15 mA (depending on the model), the ground fault protection will automatically trigger, cutting power to the floor heating system.