Toshiba RAV-SM1103DT-A Installation Manual page 14

Concealed duct high static pressure type
Hide thumbs Also See for RAV-SM1103DT-A:
Table of Contents

Advertisement

Concealed Duct High Static Pressure
Wire connection change of fan motor
Wiring connection of the fan motor is connected that external static pressure makes to 200P during
factory setting. In cases where external static pressure is required to change by the duct resistor, change
the wiring connection. The fan motor connector is connected to the 9P white color connector during
factory setting. When the fan motor is set to high static pressure, connect to the 9P red color connector
such as arrow mark. In addition, 9P red color connector is bundled along with wirings into the electric
parts box.
White color
connector
White color
connector
13-EN
2
Brown
RC
White
1
3
4
5
6
9
1
3
4
5
6
7
9
Gray
FM
White
In case of normal condition
(factory setting)
Red color connector
Brown
White
Gray
1
3
4
5
White color
1
3
4
5
connector
White
In case of high static pressure
– 13 –
Installation Manual
Red
Red
5
6
43F3
3
4
Blue
Gray
7
9
6
7
9
Gray
FM
Red
5
6
5
6
43F2
43F1
3
4
3
4
Black
Black
Blue
Closed end
connector