16 − Vent connectors serving Category I appliances shall
not be connected to any portion of mechanical draft
systems operating under positive pressure such as
Category III or IV venting systems.
17 − If vent connectors are combined prior to entering the
common vent, the maximum common vent capacity
listed in the common venting tables must be reduced by
10%, the equivalent of one 90° elbow (0.90 x maximum
common vent capacity).
18 − The common vent diameter must always be at least as
large as the largest vent connector diameter.
19 − In no case, shall the vent connector be sized more than
Capacity of Type B Double−Wall Vents with Type B Double−Wall Connectors
Height
Lateral
H
L
(m)
(m)
0
0.6
1.8
1.2
1.8
0
0.6
2.4
1.5
2.4
0
0.6
3.0
1.5
3.0
0
0.6
1.5
4.5
3.0
4.5
0
0.6
1.5
6.0
3.0
4.5
6.0
0
0.6
1.5
9.0
3.0
4.5
6.0
9.0
NOTE − Single appliance venting con gurations with zero lateral lengths are assumed to have no elbows in the vent system. For all other
vent con gurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45°
elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi-
mum listed capacity).
12
Serving a Single Category I Appliance
76mm
Appliance Input Rating in Thousands of Btu Per Hour
MIN
MAX
MIN
0
78
13
51
21
49
25
46
0
84
12
57
23
53
28
49
0
88
12
61
23
57
30
51
0
94
11
69
22
65
29
59
35
53
0
97
10
75
21
71
28
64
34
58
48
52
0
100
9
81
21
77
27
70
33
64
56
58
NA
NA
VENTING
two consecutive table size diameters over the size of
the draft hood outlet or ue collar outlet.
20 − Do not install a manual damper, barometric draft regu-
lator or ue restrictor between the furnace and the
chimney.
21 − When connecting this appliance to an existing dedi-
cated or common venting system, you must inspect the
venting system's general condition and look for signs
of corrosion. The existing vent pipe size must conform
to these instructi o ns and the provided venting tables. If
the existing venting system does not meet these re-
quirements, it must be resized.
Vent and Connector Diameter − D (mm)
100mm
MAX
MIN
0
152
18
97
30
94
36
91
0
165
16
109
32
103
39
98
0
175
17
118
32
113
41
104
0
191
15
136
30
130
40
121
48
112
0
202
14
149
29
143
38
133
46
124
55
116
0
213
13
166
28
160
37
150
44
141
53
132
73
113
125mm
MAX
MIN
0
251
27
157
39
153
47
149
0
276
25
178
42
171
51
164
0
295
23
194
41
187
54
176
0
327
20
226
39
219
51
206
61
195
0
349
18
250
38
242
50
229
59
217
69
206
0
374
14
283
36
275
48
262
57
249
66
237
88
214
104
150mm
MAX
0
375
32
232
50
227
59
223
0
415
28
263
53
255
64
247
0
447
26
289
52
280
67
267
0
502
22
339
49
330
64
315
76
301
0
540
20
377
47
367
62
351
73
337
84
322
0
587
18
432
45
421
59
405
70
389
80
374
346