5. Check voltage supply at the disconnect switch. The
voltage must be within the range listed on the unit's
nameplate. If not, do not start the equipment until you
have consulted with the power company and the
voltage condition has been corrected.
6. Set the thermostat for a cooling demand. Turn on
power to the indoor handler and close the air
conditioner disconnect switch to start the unit.
7. Recheck voltage while the unit is running. Power must
be within range shown on the nameplate.
8. Check system for sufficient refrigerate by using the
procedures listed under Testing and Charging
System.
Temp.
80
24 24 24 23 23 22 22 22 20 19 18 17 16 15
of air
entering
78
23 23 23 22 22 21 21 20 19 18 17 16 15 14
indoor
76
22 22 22 21 21 20 19 19 18 17 16 15 14 13
coil ºF
74
21 21 21 20 19 19 18 17 16 16 15 14 13 12
A
72
20 20 19 18 17 17 16 15 15 14 13 12 11 10
70
19 19 18 18 17 17 16 15 15 14 13 12 11 10
Wet−bulb ºF
57 58 59 60 61 62 63 64 65 66 67 68 69 70
T
Drop
C
19º
53º
air flow
DRY
BULB
All temperatures are
expressed in ºF
Figure 29. Checking Indoor Airflow over Evaporator Coil using Delta−T (DT) Chart
START: Determine how refrigerant is metered
WHEN TO CHARGE?
S
Warm weather best
S
Can charge in colder weather
CHARGE METHOD? Determine by:
S
Metering device type
S
Outdoor ambient temperature
REQUIREMENTS:
S
Sufficient heat load in structure
S
Indoor temperature between 70-80ºF
(21−26ºC)
S
Manifold gauge set connected to unit
S
Thermometers:
to measure outdoor ambient
temperature
to measure liquid line temperature
to measure suction line
temperature
506081−01 09/08
DT
B
A
72º
B
air flow
64º
DRY
BULB
INDOOR
WET
BULB
COIL
TXV
65ºF
(18.3ºC) and
Above
APPROACH OR
SUBCOOLING
Figure 30. Determining Charge Method
SETTING UP TO CHECK CHARGE
1. Close manifold gauge set valves. Connect the center
manifold hose to an upright cylinder of HFC−410A.
2. Connect the manifold gauge set to the unit's service
ports as illustrated in figure 1.
low pressure gauge to suction line service port
D
high pressure gauge to liquid line service port
D
INDOOR AIRFLOW CHECK
Check airflow using the Delta−T (
illustration in figure 29.
DETERMINING CHARGE METHOD
Use the illustration in figure 30 to determine the correct
charging method.
1. Determine the desired DT Measure entering air temperature
using dry bulb (A) and wet bulb (B). DT is the intersecting value of A
and B in the table (see triangle).
2. Find temperature drop across coil Measure the coil's dry bulb
entering and leaving air temperatures (A and C). Temperature Drop
Formula: (T
) = A minus C.
Drop
3. Determine if fan needs adjustment If the difference between the
and the desired DT (T
measured T
Drop
justment is needed. See examples: Assume DT = 15 and A temp. =
72º, these C temperatures would necessitate stated actions:
DT
T
Drop
53º
19
15
58º
14
15
62º
10
15
4. Adjust the fan speed See indoor unit instructions to in-
crease/decrease fan speed.
Changing air flow affects all temperatures; recheck temperatures to
confirm that the temperature drop and DT are within +3º.
Which
metering
device?
64ºF
(17.7ºC) and
Below
WEIGH-IN
Page 16
DT)
process using the
–DT) is within +3º, no ad-
Drop
=
ºF ACTION
=
4
Increase the airflow
=
−1 (within +3º range) no change
=
−5 Decrease the airflow
RFC
40ºF
(4.4ºC) and
(3.8ºC) and
Above
Below
SUPERHEAT
WEIGH-IN
39ºF