Connecting the Refrigerant Pipe

Refrigerant oil
Torque wrench
Flare nut
Union
When the indoor unit is above
the outdoor unit
Indoor unit
Outdoor unit
Oil trap(Must be installed
every 10m/33ft.)
When the outdoor unit is above
the indoor unit
Outdoor unit
Oil trap(Must be installed
every 10m/33ft.)
Indoor unit
Radius
5cm/2"
Oil trap
(suction tube)
10
E-
There are two refrigerant pipes of differing diameters:
1
Remove the pinch pipe on the pipes and connect the assembly pipes to
each pipe, tightening the nuts, first manually and then with a wrench, a
spanner applying the following torque.
Spanner
N N
o o
t t
e e
N N
o o
t t
e e
2
Must use insulator which is thick enough to cover the refrigerant pipe to
protect the condensate water on the outside of pipe falling onto the floor
and the efficiency of the unit will be better.
Cut off any excess foam insulation.
3
4
Be sure that there must be no crack or wave on the bended area.
5
It would be necessary to double the insulation thickness(10mm/ ")
to prevent condensation even on the insulator when if the installed area is
warm and humid.
6
Shape an oil trap as shown in figure. The oil trap must be formed every
level difference of 10m/33ft.
A smaller one for the liquid refrigerant
A larger one for the gas refrigerant
The inside of copper pipe must be clean & has no dust.
Outer Diameter
6.35 mm (1/4")
144~176kgf•cm(
9.52 mm (3/8")
333~407kgf•cm(
12.70 mm (1/2")
504~616kgf•cm(
15.88 mm (5/8")
630~770kgf•cm(
19.05 mm (3/4")
990~1210kgf•cm(
22.23 mm (7/8")
990~1210kgf•cm(
If the pipes must be shortened refer to page 11.
Torque
7
3
~
ft•lb)
10
12
16
4
1
~
7
ft•lb)
24
29
16
16
7
9
~
ft•lb)
36
44
16
16
9
11
~
ft•lb)
45
55
16
16
~
ft•lb)
5
1
71
87
8
2
5
~
1
ft•lb)
71
87
8
2
3
8