14.3.6
Deice Operation
When outdoor pipe temperature and outdoor air temperature is low, deice operation start where indoor fan motor
and outdoor fan motor stop and operation LED blinks.
14.3.7
Demand Control
When the air-conditioner connected to Demand Response Enabling Devices (DRED), the power consumption
especially during peak hours could be controlled.
Three Demand response modes (DRM) are available
DRM1 = Compressor cut off
o
DRM2 = Operate at 50% of rated input power
o
DRM3 = Operate at 75% of rated input power
o
During DRM, the Power Indicator blinks (3 seconds ON and 0.5 seconds OFF) to indicate the compressor cut off
status.
14.3.8
Pump down Operation by CN-S
A convenience method to activate pump down operation.
Control start condition:
During power standby condition, short CN-S continuously between 1 second and 10 seconds.
o
Control stop condition:
480 seconds after pump down operation starts.
o
CN-S is shorted again during pump down operation.
o