8.13.4    If user uses timer on function in sleep mode, sleep function will pause and not resume until reaches the 
setting on time. 
8.13.5    When user uses timer off function in sleep mode(or sleep function in timer off mode), if the timing time is 
less than 7 hours, sleep function will be cancelled when reaching the setting time. If the timing time is more than 7 
hours, the machine will not stop until reaches the setting off time in sleep mode. 
 
8.14    Auto‐Restart function 
In case of a sudden power failure, the indoor main chip will restore the setting conditions before the power failure. 
The unit will resume the previous operation setting (including setting mode, temperature, fan speed, vertical swing) 
automatically after 3 minutes when power returns. 
 
8.15    Super Ionizer function   
Super ionizer function which is controlled through remote controller is available only when the unit is on. 
After the Aircon being turned on, the Ionizer function is switched on when the unit receives CODE from remote 
controller at first time, and ionizer is switched off when the unit receives the CODE again. It's a circle. 
After starting the Ionizer function, the ionizer can work only when the indoor fan motor is running. If the indoor fan 
motor is off, the ionizer also stops working, even though the Ionizer function is available.Ionizer function will not be 
off when the running mode is switched. Ionizer function will be off when the unit is turned off. 
 
8.16    Self‐clean function 
1)    Self‐Clean function is available only at cooling (including auto‐cooling and turbo) and drying mode, when the user 
presses down the button "Self‐Clean" on remote controller, "SC" icon will be displayed on the indoor temperature 
display area. After running for 13 minutes in low fan mode, the unit will get into low heating mode (anti‐cold wind 
function is not valid). When the unit keeps low heating mode for 1 min or evaporator high temp protection occurs, it 
will stop heating and get into low fan mode and keep running for another 2 minutes. Then the unit will quit from 
Self‐Clean function and turn off. 
2)    When setting the Self‐Clean function, the unit has been in Timer or Turbo function, the Timer or Turbo function 
will be cancelled and then execute Self‐Clean function. 
3)    When the unit is running Self‐Clean function, all other functions will be not available except swing/air 
direction/clean air/vent/LED display, and only receiving "Self‐Clean" code again or "turn off" code, the unit will quit 
from the function.   
4)    When the unit is running Self‐Clean function, all protection functions are valid. 
 
8.17    Follow me function 
If the indoor PCB receives the signal which results from pressing the FOLLOW ME button on remote controller, the 
buzzer will emit a sound and this indicates the follow me function is initiated. But when the indoor PCB receives signal 
which sent from remote controller every 3 minutes, the buzzer will not respond. When the unit is running with follow 
me function, the PCB will control the unit according to the temperature from follow me signal, and the temperature 
collection function of room temperature sensor will be shielded, but the error detective function of room temperature 
sensor will be still valid. 
When the follow me function is available, the PCB will control the unit according to the room temperature (T1) from 
the remote controller and the setting temperature (TS), and the action of compressor is as following: 