Installation for indoor unit

• The piping can be connected in the four ways indicated by
,
and
.
When the piping is connected to points
the knock-out either at the side or at the bottom of the unit.
IMPORTANT NOTE:
Indoor unit has no refrigerant expansion device.
Installing the wall hanging bracket
• Install the wall hanging bracket so that it is level. Use a plumb
line if necessary.
• Be sure to leave the clearance spaces. (Refer to page 4).
• If the wall hanging bracket is not level, water may drip onto the
floor.
• Install the wall hanging bracket with a fixing that is strong
enough to withstand the weight of the unit.
300
min.
,
• Before installing the wall hanging bracket, remove it from the unit
by pushing at the indicated parts at the bottom of the body.
,
or
, remove
• Fasten the wall hanging bracket to the wall with 4 or more screw
anchors through the holes near the outer edge of the bracket.
• Install the wall hanging bracket so that there is no gap between
the bracket and the wall.
• Check that the wall hanging bracket does not move.
This can cause noise during operation.
• If the unit is removed from the wall hanging bracket after installing
it onto the wall, remove it by pushing up the indicated MARKS
(
Marking the wall penetration for the
connection piping
Rear piping
• It is best for the piping to go through the wall behind the unit, so
that the unit hides the pipes.
• For this method of installation, make a 65 mm diameter hole in the
wall at point A.
120 min.
• Drill a 65 mm diameter hole at a slope so that the outside end is
lower (5 - 10 mm) than the inside end.
This will ensure good drainage.
• Cut the wall sleeve to match the wall thickness and pass the pipe
450
through the hole.
min.
Plumb line
Side or bottom piping
• Remove the knock-out in the unit and pass the pipes through
the wall.
• The pipe should slope downward and away from the unit to
Remove screw
ensure good drainage.
) at the bottom of the body. (Refer to page 10).
450
180
E N G L I S H
110
23
245
110
Indoor side
Outdoor side
5 ~ 10 mm lower
GB - 9