Heat pump controller

Advertisement

Configuring the Heat Pump Heating System
System-specific parameters
Sets the desired return set temperature when
fixed-setpoint regulation is selected
Parallel shift of the set heating curve for heating
circuit 2. By pressing the arrow buttons once,
the heating curve is shifted by 1 °C upwards
(hotter) or downwards (colder).
Different maximum temperatures are
permissible for panel and radiator heating
systems. The upper limit of the set temperature
can be set to between 25 °C and 70 °C.
The return set temperature hysteresis forms
the neutral zone for operation of the heat pump.
The runtime between the OPEN and CLOSED
end positions varies according to the mixer
used. The mixer runtime should be adjusted to
ensure optimal temperature regulation.
Settings to lower the heating characteristic
curve of heating circuit 2
Sets the time during which the temperature in
heating circuit 2 is to be lowered.
Sets the temperature value by which the
heating characteristic curve of heating circuit 2
is to be lowered when the temperature is
lowered
For each day of the week, it is possible to select
whether Time1, Time2, no time or both times
are to be active when the temperature is
lowered. Operations to lower the temperature
that exceed a weekday are activated or
deactivated at the end of each day accordingly.
Settings to raise the heating characteristic
curve of heating circuit 2
Sets the time during which the temperature in
heating circuit 2 is to be raised.
Sets the temperature value by which the
heating characteristic curve of heating circuit 2
is to be raised.
For each day of the week, it is possible to select
whether Time1, Time2, no time or both times
are to be active when the temperature is raised.
Operations to raise the temperature that
exceed a week day are activated or deactivated
at the end of each day accordingly.
Settings for cooling operation
Does the system have dynamic cooling (fixed
return set temperature)?
Sets the desired return set temperature when
dynamic cooling is selected
Two different shut-off times are set during
which dynamic cooling is blocked
Setting range
Display
15 °C
Heating circuit 2
... 40 °C ...
Fixed-setpoint
70 °C
Indicator bar
Heating circuit 2
25 °C
Heating circuit 2
... 50 °C ...
70 °C
0.5 K
Heating circuit 2
... 2 K ...
5 K
0.5 K
Heating circuit 2
... 2 K ...
5 K
Heating circuit 2
00:00
Heating circuit 2
...
23:59
0K
Heating circuit 2
...
19 K
N
Heating circuit 2
T1
T2
Y
Heating circuit 2
00:00
Heating circuit 2
...
23:59
0K
Heating circuit 2
...
19 K
N
Heating circuit 2
T1
T2
Y
Cooling function
No
Cooling function
Yes
10 °C
Cooling function
... 15 °C...
Dyn. cooling
30 °C
00:00
Cooling function
...
Dyn. cooling
23:59
6.1
E-9