Vertical Vent Tables And Figures - Lennox MLDVT-30NM Installation Instructions Manual

Direct vent mldvt-30/35/40/45 series
Table of Contents

Advertisement

E. Support the vertical vent run sections -
Note - Proper venting support is very important.
The weight of the vent must not be supported
by the fireplace in any degree.
Support the vertical portion of the venting
system every 8 feet (2.4m) above the fireplace
vent outlet.
One method of support is by utilizing field pro-
vided support straps (conventional plumber's
tape). Secure the plumber's tape to the framing
members with nails or screws. Loop the tape
around the vent, securing the ends of the tape
to the framing. If desired, sheet metal screws #6
x 1/2" length may be used to secure the support
straps to the vent pipe. Refer to Figure 18.
F. Change vent direction to horizontal/inclined
run - At transition from or to a horizontal/in-
clined run, install the SV4.5E45 and SV4.5E90
elbows in the same manner as the straight vent
sections. The elbows feature a twist section to
allow them to be routed about the center axis
of their initial collar section to align with the
required direction of the next vent run element.
Twist elbow sections in a clockwise direction
only so as to avoid the possiblity of unlocking
any of the previously connected vent sections.
See Figure 19.
4-13/16
(122 mm)
Swivel Joint
Swivel Joint
(360° swivel)
(360° swivel)
SV4.5E45
45° Elbow)
90° Elbow)
Figure 19
G. Continue installation of horizontal/inclined
sections - Continue with the installation of the
straight vent sections in horizontal/inclined run
as described in Step C. Install support straps
every 5 ft. (1.52 m) along horizontal/inclined
vent runs using conventional plumber's tape.
See Page 17, Figure 26. It is very important
that the horizontal/inclined run be maintained
in a straight (no dips) and recommended to be
in a slightly elevated plane, in a direction away
from the fireplace of 1/4 " rise per foot (20 mm
per meter) which is ideal, though rise per foot
run ratios that are smaller are acceptable all the
way down to at or near level. Use a carpenter's
level to measure from a constant surface and
adjust the support straps as necessary.
4
It is important to maintain the required clear-
ances to combustibles: 1" (25 mm) at all sides
for all vertical runs; and 3" (76 mm) at the top,
1" (25 mm) at sides, and 1" (25 mm) at the
bottom for all horizontal/inclined runs.
H. Frame roof opening - Identify location for
vent at the roof. Cut and/or frame opening per
Roof Framing Chart (Figure 20 ).
Figure 20
I. Install the roof flashing - Extend the vent
8-/8"
7-5/8"
sections through the roof structure. Install the
(194 mm)
(206 mm)
roof flashing over the vent section and posi-
tion such that the vent column rises vertically
(use carpenters level) (Figure 21 ). Nail along
perimeter to secure flashing or adjust roofing
SV4.5E90
to overlap the flashing edges at top and sides
only and trim where necessary. Seal the top
and both sides of the flashing with waterproof
caulking.
Flashing
Figure 21
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
C
D
Framing Dimensions for Roof
Inches (millimeters)
Pitch
C
0/2
0-/2 in.
0-/2 in.
(267 mm)
(267 mm)
6/2
0-/2 in.
2 in.
(267 mm)
(305 mm)
2/2
0-/2 in.
7 3/4 in.
(267 mm)
(45 mm)
- Roof Framing
Storm
Collar
J. Install the storm collar - Install the storm
collar, supplied with the flashing, over the
vent/flashing joint. See Figure 21. Loosen the
storm collar screw. Slide collar down until it
meets the top of the flashing. Tighten the ad-
justing screw. Apply non-combustible caulking
or mastic around the circumference of the joint
to provide a water tight seal.
K. Install the vertical termination - The final
step involves installation of the SV4.5CGV-1
Vertical Termination. Extend the vent sections
to the height as shown in the "Vertical vent
termination section" in Figure 4 on Page 5.
The SV4.5CGV-1 Vertical Termination (Figure
22) can be installed in the exact same fashion
as any other Secure Vent section. Align the
termination over the end of the previously
installed section, adjusting the radial alignment
until the four locking dimples of the termination
are aligned with the inlets of the four incline
channels of the last vent section. Push the ter-
mination down until it fully engages, then twist
D
the termination clockwise running the dimples
down and along the incline channels until they
are seated at the end of the channels.
Figure 22
If the vent system extends more than 5 feet
(1.5m) above the roof flashing, stabilizers may
be necessary. Additional screws may be used
at section joints for added stability. Guide wires
may be attached to the joint for additional sup-
port on multiple joint configurations.
VERTICAL VENT FIGURES/TABLES
Note: Secure Vent (rigid vent pipe) is shown
in the Figures; Secure Flex (flexible vent pipe)
may also be used.
WARNING: UNDER NO CIRCUM-
STANCES, MAY SEPARATE SECTIONS
OF CONCENTRIC FLEXIBLE VENT
PIPE BE JOINED TOGETHER.

Advertisement

Table of Contents
loading

Table of Contents