UNIT SIZE
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb.)
COMPRESSOR QUANTITY
TYPE
REFRIGERANT
REFRIGERANT METERING DEVICE
Refrigerant (R-410A) Quantity (lb.)
ORIFICE ID (in.)
ORIFICE OD (in.)
OUTDOOR COIL
Rows... Fins/in.
face area (sq. ft.)
OUTDOOR FAN
Nominal Airflow (CFM)
Diameter
Motor HP (RPM)
INDOOR COIL
Rows... Fins/in.
face area (sq. ft.)
INDOOR BLOWER
Nominal Airflow (CFM)
Size (in.)
Motor (HP)
HIGH-PRESSURE SWITCH (psig)
Cutout
Reset (Auto)
LOSS-OF-CHARGE/LOW-PRESSURE SWITCH
(Liquid Line) (psig)
Cutout
Reset (Auto)
RETURN-AIR FILTERS (in.)*
throwaway
* Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300
ft/minute for throwaway type or 450 ft/minute for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg.
TABLE 2—MINIMUM AIRFLOW FOR RELIABLE ELECTRIC HEATER OPERATION (CFM)
SIZE
AIRFLOW (CFM)
* The 030 size models must be run on medium or high speed when used in conjunction with 15 kw electric heat accessory
CAUTION: Failure to follow these precautions could
result in damage to the unit being installed:
1. Make all electrical connections in accordance with
NEC ANSI/NFPA (latest edition) and local electrical
codes governing such wiring. In Canada, all electrical
connections must be in accordance with CSA standard
C22.1 Canadian Electrical Code Part 1 and applicable
local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between
field-supplied electrical disconnect switch and unit.
DO NOT USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within
operating voltage range indicated on unit rating plate.
On 3-phase units, ensure phases are balanced within 2
percent. Consult local power company for correction
of improper voltage and/or phase imbalance.
4. Insulate low-voltage wires for highest voltage con-
tained within conduit when low-voltage control wires
are in same conduit as high-voltage wires.
5. Do not damage internal components when drilling
through any panel to mount electrical hardware, con-
duit, etc.
TABLE 1—PHYSICAL DATA—UNIT 602B
602B024
2
299
7.0
0.061
0.032 (2)
2...17
8.5
2350
22
1/8 (825)
3...15
3.7
800
10x10
1/4
20x20x1
602B024
602B030
800
1000*
602B030
602B036
2-1/2
3
320
328
SCROLL COMPRESSOR
R-410A
Accurater
8.9
9.3
0.061
0.067
0.040 (2)
0.040 (2)
2...17
2...17
10.3
10.3
2350
2800
22
22
1/8 (825)
1/4 (1100)
3...15
4...15
3.7
3.7
1000
1200
10x10
10x10
1/4
1/2
610 ± 15
420 ± 25
20 ± 5
45 ± 10
20x20x1
20x24x1
602B036
602B042
1200
1400
A. HIGH-VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a field-
supplied, waterproof disconnect switch mounted at, or within sight
from the unit. Refer to the unit rating plate, NEC and local codes
for maximum fuse/circuit breaker size and minimum circuit amps
(ampacity) for wire sizing (See Table 3 for electrical data).
The field-supplied disconnect may be mounted on the unit over the
high-voltage inlet hole (See Figs. 2 and 3).
If the unit has an electric heater, a second disconnect may be
required. Consult the Installation, Start-Up, and Service Instruc-
tions provided with the accessory for electrical service connec-
tions.
Operation of unit on improper line voltage constitutes abuse and
may cause unit damage that could affect warranty.
B. ROUTING POWER LEADS INTO UNIT
Use only copper wire between disconnect and unit. The high-
voltage leads should be in a conduit until they enter the duct panel;
conduit termination at the duct panel must be watertight. Run the
high-voltage leads through the power entry knockout on the power
entry side panel. (See Fig. 2 and 3 for location and size) When the
leads are inside the unit, run leads up the high-voltage raceway to
the line wiring splice box. (See Fig. 13 through 15) For single-
—8—
602B042
602B048
3-1/2
4
350
355
1
9.5
10.6
0.073
0.076
0.038 (2)
0.046 (2)
2...17
2...17
13.5
13.5
2500
3300
22
22
1/8 (825)
1/4 (1100)
3...15
4...15
4.7
4.7
1400
1600
11x10
11x10
1/2
1/2
24x30x1
24x30x1
602B048
1600
602B060
5
428
12.4
0.088
0.052 (2)
2...17
15.4
3300
22
1/4 (1100)
4...15
5.7
1750
11x10
1
24x30x1
602B060
2000