DIP switch setting

I Checking according to dip switch setting
1. You can check the setting values of the main outdoor unit from the 7 segment LED.
The dip switch setting should be changed when the power is OFF.
2. It checks whether the input is properly performed without the bad contact of the dip switch or not
I Checking the setting of the Master unit
The number is sequentially appeared at the 7 segment in 5 seconds after applying the power. This
Number represents the setting condition.(For example, represents 3Ø 208/230V 20HP heat pump)
Master model code ¡ Slave1 model code ¡ total capacity ¡ 2 ¡ 25 ¡ 140
1~255 : Master model code
1~255 : Master model code
1~255 : Master model code
5~48 HP : HP number (Sum of Master capacity and Slave capacity)
No display : cooling only
25 : Normal
140 : 3Ø 208/230V
Example) 3Ø 208/230V 20HP heat pump
151 ¡ 151 ¡ 20 ¡ 2 ¡ 25 ¡ 140
CAUTION
Product may not properly operate if the relevant DIP switch is not properly setup.
Model Code
3Ø 208/230V
Model Code
Unit (HP)
150
8
151
10
152
12
2 : Heat pump
3: Sync
160 : 3Ø 460V
3Ø 460V
Model Code
Unit (HP)
171
172
10
173
12
174
14
175
16
8
Electrical Wiring
Installation Manual 59