◆ Daily maintenance
Cleaning of air filter
If
is displayed on the remote controller, maintain the
air filter.
1
Push the
button to stop the
operation, then turn off the circuit breaker.
After the cooling or dry operation, the
ventilation fan keeps running for self-
cleaning. Push the
button twice to
stop the operation.
3
Take out the air filter
1
Open the air intake grille until it stops, and
slightly raise the hook on the lower centre of
the air filter.
The air intake grille should not be opened further;
otherwise, the arms may come off and the air
intake grille may fall down.
Cleaning with water or vacuum cleaner
• If dirt is heavy, clean the air filter by tepid water with
neutral detergent or water.
• After cleaning with water, dry the air filter sufficiently
in a shade place.
39-EN
Mount the air filter
2
Turn on the circuit breaker, then push the
button on the remote controller to
start the operation.
3
After cleaning, push
.
display disappears.
1,2
CAUTION
• Do not start the air conditioner while leaving air filter removed.
• Push the filter reset button. (
indication will be turn off.)
◆ Periodic maintenance
For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air conditioner
in use be cleaned and maintained regularly to ensure efficient operation of the air conditioner.
When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended.
Furthermore, regularly check the outdoor unit for rust and scratches, and remove them or apply rustproof
treatment, if necessary.
As a general rule, when an indoor unit is operated for 8 hours or more daily, clean the indoor unit and outdoor unit
at least once every 3 months. Ask a professional for this cleaning / maintenance work.
Such maintenance can extend the life of the product though it involves the owner's expense.
Failure to clean the indoor and outdoor units regularly will result in poor performance, freezing, water leakage, and
even compressor failure.
Inspection before maintenance
Following inspection must be carried out by a qualified installer or qualified service person.
Parts
Access from inspection opening and remove the access panel. Examine the heat exchanger if there
Heat exchanger
is any clogging or damages.
Fan motor
Access from inspection opening and check if any abnormal noise can be heard.
Access from inspection opening and remove the access panel. Examine the fan if there are any
Fan
waggles, damages or adhesive dust.
Filter
Go to installed location and check if there are any stains or breaks on the filter.
Access from inspection opening and remove the access panel. Check if there is any clogging or drain
Drain pan
water is polluted.
▼ Maintenance list
Part
Unit
Check (visual / auditory)
Dust / dirt clogging,
Heat exchanger
Indoor / outdoor
scratches
Fan motor
Indoor / outdoor
Sound
Filter
Indoor
Dust / dirt, breakage
• Vibration, balance
Fan
Indoor
• Dust / dirt, appearance
Air intake /
Indoor / outdoor
Dust / dirt, scratches
discharge grilles
Dust / dirt clogging, drain
Drain pan
Indoor
contamination
Ornamental panel,
Indoor
Dust / dirt, scratches
louvres
• Rust, peeling of insulator
Exterior
Outdoor
• Peeling / lift of coat
– 20 –
Inspection method
Maintenance
Wash the heat exchanger when it is clogged.
Take appropriate measures when abnormal sound is
generated.
• Wash the filter with water when it is contaminated.
• Replace it when it is damaged.
• Replace the fan when vibration or balance is
terrible.
• Brush or wash the fan when it is contaminated.
Fix or replace them when they are deformed or
damaged.
Clean the drain pan and check the downward slope
for smooth drainage.
Wash them when they are contaminated or apply
repair coating.
Apply repair coating.