Cooling capacities sensitives
Outdoor
air dry
Model
temperature
°C (DB)
25
SOC-180/
35
SIC-180
45
25
SOC-240/
35
SIC-240
45
SIC-240 fan performance
Model
SIC-240
8
Total
Air
capacity
intake humid
temperature
°C (WB)
W/h
22
64 800
19.5
58 320
17
54 000
22
59 940
19.5
54 000
17
49 680
22
54 000
19.5
48 600
17
44 280
22
81 600
19.5
73 440
17
68 000
22
75 480
19.5
68 000
17
62 560
22
68 000
19.5
61 200
17
55 760
Available static pressure
mm WG
Pa
19.9
195
18
176
16.1
158
13.4
131
10.7
105
7.4
73
3.9
38
0
0
Sensitive capacity (W/h)
Temperature air going to indoor unit °C (TS)
22
24
W/h
W/h
19 662
27 333
29 237
36 909
39 432
47 104
18 017
25 689
27 641
35 313
35 362
43 034
16 187
23 859
25 819
33 491
35 525
43 197
24 781
34 373
36 750
46 343
49 500
59 092
22 707
32 300
34 737
44 330
47 088
56 681
20 400
29 992
32 441
42 033
44 575
54 168
Air flow rate
m
3
/h
10 000
11 000
12 000
13 000
14 000
15 000
16 000
17 000
Compressor
27
29
W/h
W/h
38 841
46 524
48 417
56 102
54 000
54 000
37 197
44 869
46 820
54 000
49 680
49 680
35 367
43 039
44 999
48 600
44 280
44 280
48 762
58 368
60 732
70 340
68 000
68 000
46 688
56 281
58 718
68 000
62 560
62 560
44 381
53 973
56 422
61 200
55 760
55 760
Power input
m
3
/s
2.78
1 395
3.05
1 550
3.33
1 565
3.61
1 905
3.89
2 050
4.16
2 240
4.44
2 430
4.72
2 675
absorbed
power
kW
12.60
13.20
13.80
14.25
15.00
15.75
16.50
17.25
18.00
19.65
20.58
21.52
22.22
23.39
24.56
25.73
26.90
28.07
W