Indoor Venting-General Requirements (Category I & Category Iii - Clarification); Heater Clearances; Outside Vent Removal - STA-RITE Max-E-Therm® Operation & Installation Manual

120/240 vac natural gas/lp gas pool & spa heater
Table of Contents

Advertisement

1 8
INDOOR VENTING — General Requirements
The heater may be installed as a Category I or Category III appliance.
Vented Appliance (Category I) –
An appliance that operates with a nonpositive vent static pressure and with a vent gas temperature that avoids excessive
condensate production in the vent, see
Vented Appliance (Category III) –
An appliance that operates with a positive vent static pressure and with a vent gas temperature that avoids excessive
condensate production in the vent, see
If you are considering connecting this heater to a pre-existing vent system, make sure that the vent system meets the
appropriate venting requirements as given in this manual on
a draft hood with this heater.
The vent pipe must be the same size or larger. The Max-E-Therm
and with a vent gas temperature less than 400° F. The total length of the horizontal run must not exceed the length that is
listed in
table 11
on
page
23.
HEATER CLEARANCES — General Requirements
INDOOR INSTALLATION (U.S.) OR OUTDOOR SHELTER (CANADA)
The following clearances must be maintained from combustible surfaces:
TOP .............................. 6 in. (15 cm)
ALL SIDES .................. 6 in. (15 cm)
VENT............................ 6 in. (15 cm)
Note: The heater is design certified by CSA International for installation
on combustible flooring. For installation on carpeting, the heater must be
mounted on a metal or wood panel that extends at least three inches
(10cm) beyond the base of the heater. If the heater is installed in a
closet or alcove, the entire floor shall be covered by the panel. On an
outdoor shelter installation, the exhaust discharges into a vent pipe.
Orient the heater so that the vent pipe does not interfere with adjustment
of the operating controls. The operating control panel, located on the top
of the jacket, can be rotated for convenient access to the control panel.
OUTSIDE VENT COVER REMOVAL
The heater is supplied from the factory with a built-in stackless outside
vent for outdoor installation. Remove the outside vent cover for outdoor
shelter installation.
P/N S794
Vertical only
pages
20-22.
Vertical or Horizontal
pages
23-25.
pages
Section 2. Installation
18-27. If not, replace the vent system. DO NOT use
®
heaters operate with a positive vent static pressure
6 in.
6 in.
6 in.
6 in.
Figure 12.
Rev. B 6-23-08