9-2 Refrigerating Cycle Diagram
Indoor Unit
Heat
Exchanger
(Evaporator)
Cooling
Gas leak check point
Amount of refilling per extension length of 1mm; when extending the pipe length by more
than 7.5m, "A" g of R410 , refrigerant should be refilled per extension length of 1m.
Model
UH140GAMC
UH105GAMC
UH070EAMC
UH052EAMC
UH094EAM1C
Samsung Electronics
3-Way valve
Liquid pipe
Gas pipe
3-Way valve
"A" g
70g
70g
40g
25g
60g
Outdoor Unit
Filter
Expansion
valve
Accumulator
Compressor
Filter
Heat
Exchanger
(Condenser)
Muffle
9-3